Page 2

background image

TDR2000/2 (CFL535F)

Cable Fault Locator

Interactive Help Screen

A full graphical help screen is available with keyboard

layout and individual key operation. At the press of a

button.

Trace Storage

15 internal trace memories provide for the storage and

recall of test results. The traces can be recalled to the

display for analysis or compared with an active display to

aid in fault location.

Alternatively the stored results can be downloaded to a

computer, over the RS232 port, using the TraceMaster

software and RS232 lead provided.

Trace Master PC Software

Trace Master provides download and upload facilities

between the TDR and a computer. Traces can be

individually selected, saved to a PC and annotated by the

user. Historical information can be reviewed on the PC or

recalled to the TDR for comparison with current

measurements. Trace-Master is the ideal tool for cable

documentation. Results can be printed from the computer

for inclusion in documents.

Power source

The TDR2000/2 can be supplied as a standard battery

powered unit or in a rechargeable version, as the

TDR2000/2RM or TDR2000/R. Fitted with a NiMH

rechargeable battery pack the TDR2000/2R and

TDR2000/RM are supplied with the charger as standard.

BENEFITS

I

11 fault location modes

I

For use on Telecom TNV-3 circuit, or 300V CAT III

power circuits with fused leads. Phase to Earth or 415 V

Phase to Phase

I

External mains blocking filter not required

I

Screen contrast control

I

Multi language operation, uploadable using

TraceMaster software

I

3 step pulse amplitude control

I

Adjustable display contrast

I

15 trace internal memory

I

Protected to IP54

I

High impact ABS case

I

Comes with test and carry case and test leads

SPECIFICATION

Except where otherwise stated, this specification applies at an

ambient temperature of 20° C.

Ranges

50 m, 100 m, 200 m, 400 m, 1 km, 2 km, 4 km, 8 km, 16 km

(150 ft, 300 ft, 600 ft, 1200 ft, 3000 ft, 6000 ft, 12000 ft, 24000 ft,

48000 ft)

Resolution

0.1 m (4in.) up to 200 m (600 ft)

0.2 m (8 in.) up to 400 m (1200 ft)

0.1% of range above 400 m (1200 ft)

Measurement Accuracy

0.1% of Range

[Note – The measurement accuracy is for the indicated cursor

position only and is conditional on the velocity being correct]

Input Impedance: 120

Ω.

Input Protection: 300 V CATIII working, 415 V CATIII Phase to

Phase

Output Pulse Amplitude

Nominal 3 V, 5 V and 14 Vpk to pk into an open circuit

Pulse width user selectable:
50m range:

7 ns, 20 ns, 40 ns,

150 ft

60 ns, 80 ns

100m range:

7 ns, 40 ns, 60 ns,

300 ft

80 ns, 100 ns

200 m ranges: 7 ns, 40 ns, 80 ns,

600 ft

140 ns, 200 ns

400 m range:

40 ns, 80 ns, 160 ns,

1200 ft

200 ns, 400 ns

1km range:

80ns, 160ns, 260 ns,

3000 ft

500 ns, 1 ms

2km range:

160 ns, 260 ns,

6000 ft

500 ns, 1 ms, 2 ms

4km range:

240 ns, 500 ns,

12000 ft

1 ms, 2 ms, 4 ms

8km range:

500 ns, 1 ms, 2 ms,

24000 ft

4 ms, 8ms

16km range:

1 ms, 2 ms, 4 ms,

48000 ft

8 ms, 16 ms

(Default pulse width for each range underlined)

Gain: 0 to 90 dB in steps of 6 dB

Velocity Factor

Variable from 0.300 to 0.999 in steps of 0.001

TX Null: 0

Ω to 120 Ω

Screen Update Rate

Once per second or three times per second, (user selectable).

Power Down

Automatic after 5, 10 or 15 minutes with no keys pressed,

(user selectable).

Backlight

Stays on for 1, 2 or 5 minutes when activated, (user selectable).

Communications Port

RS-232C compatible 1 start bit, 8 data bits, 1 stop bit and no

parity, 19200 baud standard

Internal Memory: Storage capacity of 15 waveforms and data