Atec OMICRON-CMA-156 User Manual
Amplifier units
Amplifier Units
CMA 156: 6 Phase Current Amplifier (6 x 25 A)
VEHV1010
CMA 156 amplifier units can be used in combination with any CMC test set or in conjunction
with digital real time power system network simulators. The outputs are galvanically separated
from the inputs as well as from ground and are used independently or in addition to those
of the CMC test sets.
The CMA 156 contains six independent current channels, arranged in two isolated groups
(A, B). The outputs can be configured in various ways (connected in parallel, in series, etc.).
For example, by using four CMA 156 units, 3 x 200 A can be generated. The connection to a
CMC test set is made by a control cable at the back of the units.
Used for tests requiring more current channels than provided by the CMC test sets.
Amplifiers, general
Input impedance
> 40 kW
Galvanic isolation Input/Output
1.5 kVDC
Galvanic isolation amplifier groups
1.5 kVDC
Connection
4 mm (0.16 in) banana sockets /
combination socket
Amplifiers, if controlled by a CMC
Frequency
range sine signals
10 ... 1000 Hz
range transient signals DC ... 3.1 kHz
accuracy/-drift
±0.5 ppm / ±1 ppm
resolution
5 µHz
Phase
angle range
- 360° ... +360°
resolution
0.001°
error at 50/60 Hz
< 0.02° typ., < 0.1° guar.
Output current resolution
1 mA
Power supply
Nominal input voltage
110 – 240 VAC, 1-phase
Permissible input voltage
99 ... 264 VAC
Nominal frequency
50/60 Hz
Permissible frequency range
45 ... 65 Hz
Power consumption
< 1000 VA
Connection
Standard AC socket (IEC 60320)
Environmental conditions
Operation temperature
0 ... +50 °C (+32 ... +122 °F)
Storage temperature
-25 ... +70 °C (-13 ... +158 °F)
Humidity range
Relative humidity 5 ... 95 %,
non-condensing
Vibration
IEC 60068-2-6 (20 m/s
2
at 10 ... 150 Hz)
Shock
IEC 60068-2-27 (15 g/11ms half-sine)
EMC
Emission
Immunity
Directive 2004/108/EC (CE conform)
EN 61326-1, EN61000-6-4, EN61000-3-2/3
FCC Subpart B of Part 15 Class A
EN 61326-1, EN61000-6-2,
EN 61000-4-2/3/4/5/6/11
Safety
Directive 2006/95/EC (CE conform)
EN 61010-1, EN 60950-1, UL 61010-1,
CAN/CSA-C22.2 No 61010-1-04
Miscellaneous
Weight
15.4 kg (34.0 lbs)
Dimensions
(W x H x D, without handle)
450 x 145 x 390 mm
(17.7 x 5.7 x 15.4 in)
Certifications
TÜV-GS
Current amplifiers
2
Setting range
6-phase AC (L-N)
6 x 0 ... 25 A
3-phase AC (L-N)
3 x 0 ... 50 A (Group A II B)
1-phase AC (L-N)
1 x 0 ... 150 A
(Group A II B)
DC (L-N)
2 x 0 ... ±25 A
1 x 0 ... ±50 A
Power
6-phase AC (L-N)
6 x 70 VA at 7.5 A
3-phase AC (L-N)
3 x 140 VA at 15 A (Group A II B)
1-phase AC (3L-N)
1 x 420 VA at 22.5 A
1 x 420 VA at 45 A (Group A II B)
1-phase AC (L-L)
1 x 280 VA at 7.5 A
DC (L-N)
2 x 140 W at ±10.5 A
1 x 280 W at ±21 A (Group A II B)
3/6 phase operation
6-phase AC (L-N)
160
Output current / A
120
80
40
0
0
10
20
30
40
50
3-phase AC (A II B)
Output po
w
er / V
A
per phase
single phase operation
Output current / A
0
25
A(L-L) and
B(L-L) in
series
50
75
100
125
150
400
300
200
100
A(3L-N) and
B(3L-N) in series
A(3L-N) and B(3L-N)
in parallel
0
Output po
w
er / V
A
Accuracy
error < 0.03 % typ., < 0.1 % guar.
Distortion (THD+N)
3
< 0.1 % typ., < 0.3 % guar.
Bandwidth (-3dB)
> 8 kHz
Phase lag at 50/60 Hz
1.07°/1.28°
Input voltage
0 ... 5 V
Amplification
5 A / V
Max. compliance voltage (L-N)/(L-L)
15 Vpk / 60 Vpk
1
Guaranteed values valid over one year within 23 °C ±5 °C (73 °F ±10 °F), in the
frequency range of 10 ... 100 Hz at nominal value. Specifications for three-phase
systems under symmetrical conditions (0°, 120°, 240°).
2
For higher current/power requirements: CMA units can be switched in parallel
3
THD+N: Values at 50/60 Hz with 20 kHz bandwidth
Technical Data
1
Document Outline
- Test Set Overview
- CMControl
- Test Universe Software
- Software
- QuickCMC
- State Sequencer
- Ramping
- TransPlay: Transient Playback Tool
- Harmonics
- Binary I/O Monitor
- CB Simulation
- Pulse Ramping
- Overcurrent
- Overcurrent Characteristics Grabber
- Distance
- Differential
- Autoreclosure
- Advanced Distance
- VI Starting
- Advanced Differential
- Annunciation Checker
- Synchronizer
- Transient Ground Fault
- Advanced TransPlay
- Meter
- Transducer
- OMICRON Control Center
- Pause Module, Text View, ExeCute
- Test Object Definition with XRIO ®
- PTL Protection Testing Library
- CM Engine Programming Interface
- cm_FCS Field Calibration Software
- QuickCMC
- Additional Software
- NetSim Network Simulation Software
- EnerLyzer TM
- TransView
- PQ Signal Generator
- NetSim Network Simulation Software
- IEC 61850 Testing Tools
- IEDScout
- GOOSE
- Sampled Values (SV)
- IEC 61850 Package
- SVScout
- CMC 850 Package
- IEDScout
- Scheme Testing Tools
- CommPro
- LogicPro
- DLogicPro
- CommPro
- Test Sets
- CMC 356: 6 Phase Current + 4 Phase Voltage Test Set and Commissioning Tool
- CMC 353: 3 Phase Current + 4 Phase Voltage Test Set and Commissioning Tool
- CMC 256plus: 6 Phase Current + 4 Phase Voltage Test Set and Universal Calibrator
- CMControl: Front Panel Control for CMC Test Sets
- CMC 850: IEC 61850 Test Set
- CMC 356: 6 Phase Current + 4 Phase Voltage Test Set and Commissioning Tool
- Amplifier Units
- CMA 156: 6 Phase Current Amplifier (6 x 25 A)
- CMS 156: 3 Phase Voltage and Current Amplifier (3 x 250 V, 3 x 25 A)
- CMA 156: 6 Phase Current Amplifier (6 x 25 A)
- Accessories
- CMGPS Synchronization Unit
- CMIRIG-B Interface
- CMB IO-7
- Scanning Heads and Related Accessories
- Cable Connector for REF 54x
- CMLIB A Low Level Signal Connector
- CPOL Polarity Checker
- C-Probe 1 Current Clamp
- C-Shunt 1
- C-Shunt 10
- Converter optical – electrical
- CMUSB-P USB to Parallel Converter
- Generator Combination Cable
- CMC Wiring Accessory Package
- Standard CMx Accessories
- Transport Cases
- Foldable Stand
- CM Recloser and Sectionalizer Test Cables
- CMGPS Synchronization Unit
- Other Test Equipment
- CPC 100 & CP CU1
- CT Analzyer
- Contacts
- CT Analzyer
- CPC 100 & CP CU1