beautypg.com

Ms-2 circuit breaker and overload relay test set, Ordering information – Atec Megger-Multi-Amp-MS-2 User Manual

Page 2

background image

MS-2

Circuit Breaker and Overload Relay Test Set

The test set is capable of testing the time-delay characteristics of
devices rated up to 125 A using a test current of three times their
rating (375 A). Additionally, to perform an instantaneous trip test,
it will provide 750 A through a typical, 125 A, molded-case circuit
breaker connected with the test leads provided with the test set.
Overload Capability: To increase use of the test set, it is
designed so that the current ratings may be exceeded for short
durations. Because the magnitude of the output current is
determined by the impedance of the load circuit, the voltage
rating must be sufficient to push the desired current through the
device under test and the connecting test leads.

Percent Rated

Maximum

Minimum

Current

Time On

Time Off

100 (1x)

30 min

30 min

200 (2x)

3 min

8 min

300 (3x)

30 s

4 min

400 (4x)

7 s

2 min

Output Initiate Circuit: The test set uses a solid-state output
initiating circuit. To increase reliability and eliminate contact
maintenance, this circuit uses a triac instead of a contactor to
initiate the output.
The initiating circuit provides momentary and maintained modes
to control output duration. The momentary mode is used
whenever the output is to be on for a short duration, such as
when performing instantaneous trip tests, or to avoid damage or
overheating of the device under test while setting the test current.
In the maintained mode, the output remains energized until
manually turned off or, when performing timing tests, until the
device under test operates — which both stops the timer and
de-energizes the output.

INSTRUMENTATION
Ammeter

Operating Modes (switch-selected)
Memory
Normal

Display
3

1

/2

digit, extra-bright LED display with 0.3 in. (7.62mm) numerals

Ranges (switch-selected)
0 to 1.999/19.99/199.9/750 A

ContinousAccuracy (overall ammeter system)
±1% of reading, ±1 digit on three high ranges
Regulating: ±1% of range, ±1 digit on low range

Timer

Display
5-digit, extra-bright, LED display with 0.3 in. (7.62mm) numerals

Ranges (switch-selected)
0 to 99.999 s
0 to 999.99 s
0 to 99999 cycles

Accuracy
±0.005% of reading, ±1 digit

Timer Control Circuit

This circuit automatically starts the timer when the output is
energized and automatically stops the timer and de-energizes the
output when the device under test operates. This circuit
accommodates the following test conditions by simple switch
selection of the appropriate mode:
Current Actuated: Used to test a device that has no auxiliary
contacts to monitor, such as a single-pole circuit breaker. The
timer stops when the output current is interrupted.
Normally Closed: Used to test a device with normally closed
contacts. The timer stops and the output is de-energized when the
contacts open.
Normally Open: Used to test a device with normally open
contacts. The timer stops and the output is de-energized when the
contacts close.

Enclosure

The test set is housed in a high strength, molded, suitcase-type
enclosure with carrying handle and removable cover. Storage
space is provided for test leads.

Dimensions

9.9 H x 14 W x 11 D in.
(25 H x 35 W x 28 D cm)

Weight

33 lb (15 kg)

Item (Qty)

Cat. No.

Model MS-2

115 volt input

MS-2-115

230 volt input

MS-2-230

Included Accessories

Timer control circuit leads, 5 ft (1.5 m) [2]

1282

Test and maintenance record cards

Green [50]

2239

Buff [50]

2238

ORDERING INFORMATION

Item (Qty)

Cat. No.

No. 4 high-current leads, 5 ft (1.5 m) [2]

2265

Fuses

5 A, 250 V, MDA [5]

952

0.125 A, 250 V, MDL [5]

981

10 A, 250 V, MDA [5]

984

0.0625 A, 250 V, MDL [5]

987

Instruction manual [1]

8470

UK

Archcliffe Road Dover
CT17 9EN England
T +44 (0) 1304 502101
F +44 (0) 1304 207342

UNITED STATES

4271 Bronze Way
Dallas TX75237-1088 USA
T 800 723 2861 (USA only)
T +1 214 330 3203
F +1 214 337 3038

OTHER TECHNICAL SALES OFFICES

Valley Forge USA, Toronto CANADA,
Mumbai INDIA, Trappes FRANCE,
Sydney AUSTRALIA, Madrid SPAIN
and the Kingdom of BAHRAIN.

Registered to ISO 9001:2000 Reg no. Q 09290

Registered to ISO 14001 Reg no. EMS 61597

MS2_DS_en_V10

www.megger.com
Megger is a registered trademark