Peak kilovolts, Cable capacitance microfarads, Output peak milliamperes – Atec High-Voltage-VLF-28CMF User Manual
Page 5
PEAK
KILOVOLTS
0
60
CABLE CAPACITANCE
MICROFARADS
0
60
0
6.0
OUTPUT PEAK MILLIAMPERES
SCOPE
POS
NEG
60
30
10
METER
μF
mA
CAPACITANCE
SCALE X10
PUSH TO READ
X1
CAP
ZERO
5
Input:
230 V, 50/60 Hz, 30A peak, 25A average
Output:
0-65 kVac peak, 0.1/0.05/0.02/0.01 Hz sinusoidal
Duty:
Continuous
Load Rating:
2.2 mF @ 0.1 Hz, 4.4mF @ 0.05 Hz
11 mF @ 0.02 Hz & 22 mF @ 0.01 Hz
Metering:
Voltmeter: 0-75 kVac peak
Charging Current Meter: 0 – 200 mA peak
Load capacitance meter: 0 – 6 microfarads
User programmable test duration timer
Cable Lengths: Shielded EPR output cable - 100 ft. (30m)
Ground cable 100 ft. (30m)
Sizes & Weight: Controls: 17” w x 11” d x 9.5” h, 20 lbs.
432mm w x 280mm d x 241mm h, 9 kg
Regulator: 20” w x 14” d x 27” h, 160 lbs.
508mm w x 356mm d x 686mm h, 73 kg
HV Tank: 15” w x 18” d x 22” h, 215 lbs.
381mm w x 457mm d x 559mm h, 98 kg
Overall:
30” w x 60” d x 51” h, 704 lbs.
762mm w x 1524mm d x 1295mm h, 320 kg
VLF-65CMF
The VLF-65CMF, 65 kVpeak output, is a higher power model designed to test
very long cables rated up to 35kV. It offers the complete controls package including
Cable Burn mode. Its cable reels provide 100’ (30m) of HV and ground cable.
VLF-90CMF
The
VLF-90CMF offers 90kVac peak output voltage, suitable for testing
cables rated 45 – 50kV. It is load rated for 0.55
m
F @ 0.1Hz, capable of test-
ing up to 2 miles of cable, five times that at 0.02Hz. Pictured with optional
hand truck.
Input:
230 V, 50/60 Hz, 20A peak, 15A average
Output:
0-90 kVac peak, 0.1/0.05/0.02 Hz sinusoidal
Duty:
Continuous
Load:
.55 mF @ 0.1 Hz
1.1 mF @ 0.05 Hz
2.75 mF @ 0.02 Hz
Metering:
Voltmeter: 0-100 kVac peak
Current Meter: 0 – 100 mA peak
Load capacitance: 0 – 6 microfarads
User programmable test duration timer
Cable Lengths: Shielded EPR output cable – 20 ft. (6m)
Interconnect cable - 10 ft. (3m)
Sizes & Weights: Control: 26” w x 13” d x 16” h, 75 lbs.
660 mm w x 330 mm d x 406 mm h, 34 kg
HV Tank: 15” w x 21” d x 29” h, 293 lbs.
381 mm w x 533 mm d x 737 mm h, 133 kg
Input:
230V +/-10%, 50/60 Hz, single phase, 30 A peak, 25 A avg.
Output:
Sinusoidal 0-50 kVac peak, 0.1, .05, .02 and .01 Hz frequency
Duty:
Continuous
Test Capacitance:
5.0mF @ .1 Hz, 10.0mF @ .05 Hz, 25.0 mF @ .02 Hz, [email protected] Hz
Minimum capacitance to achieve full output – .01 mF
Kilovoltmeter: 3.5 in., 0-60 PEAK KILOVOLTS 2% FS Accuracy
Current Load:
3.5 in., 0-200 MILLIAMPERES 5% FS Accuracy
Capacitance Meter:
0-6 mF with x1 & x10 ranges
Sizes:
Remote Control: 17” w x 11” d x 9.5” h, 20 lbs.
432mm w x 280mm d x 241mm h, 9 kg
Power Section: 20” w x 14” d x 27” h, 160 lbs.
508mm w x 356mm d x 686mm h, 73 kg
HV Tank size:
13.5” w x 19” d x 23” h, 310 lbs.
343mm w x 483mm d x 584mm h, 141 kg
Complete Trolley: 28” w x 60” d x 51” h, 775lbs
711mm w x 1524mm d x 1295mm h, 352 kg
Output cable
length:
Shielded X-Ray/Ground on reels - 100ft.
VLF-50CMF
The VLF-50CMF is the highest power VLF unit we offer. It is rated for 5 mF at 0.1 Hz and can increase its output to 50 mF at 0.01
Hz, capable of testing up to 50 miles of 15 kV and 25 kV cable. It is ideal for very long cable runs, like long feeders, wind farm
applications, submarine cables, and others. It comes as pictured, including a cable reels with 100’ of high voltage and ground cable.
Remove the wheels for van mounting.
Simple installation – ready to go.
VLF-65CMF
Wind Farm
Model
VLF-50CMF
Remove
wheels
for van
mounting
Only portable
unit at 90 kV