Technical data design order codes – Atec HV-Diagnostics-HVA30 User Manual
Page 2
![background image](/manuals/318989/2/background.png)
Input Voltage
110-230 V 50 / 60 Hz (400 VA)
Output Voltage
Sinusoidal: 0-33 kV peak, symmetrical, 23kV rms
DC: ± 0-30 kV
Squarewave: 30kV
Accuracy: ± 1%; resolution: 0,1kV
Output Current
0-15mA (resolution 1μA), accuracy: ± 1 %
Resistance Range
0.1 MΩ ….5 GΩ
Output Frequency
0.01….0.1 Hz in steps of 0.01 Hz (default 0.1Hz) – auto frequency selection
Output Load
0.5μF @ 0.1Hz @ 23kV RMS (Approx 1,500m / 5,000ft of cable)*
1.0μF @ 0.05Hz @ 23kV RMS (Approx 3,000m / 10,000ft of cable)*
2.5μF @ 0.02Hz @ 23kV RMS (Approx 8,000m / 25,000ft of cable)*
12.0μF maximum Capacitance
* Based on a typical cable: 100pF/ft or 300pF/m
Output Modes
AC (VLF) symmetrical and load independent across full range
DC (positive or negative polarity)
Burn / Fault Condition or Fault Trip Mode
Jacket / Sheath Testing
Protection
50 and 60Hz and RMS Voltage 12kV feedback protection
Input surge arrestors (use only voltage regulated generators)
Memory
50 test records stored in non-volatile built in memory
Metering
Voltage and Current (True RMS and/or peak), Capacitance, Resistance, Time, Flashover Voltage
Duty
Continuous - no thermal limitation for operating time.
HV Cable
4.5m (15’) with Alligator clamps on end (other options available on request)
Computer Interface
RS232 connection (Software Included), USB Flash Drive
Temperature
Storage: -25ºC to +70ºC Operating: -5ºC to +45ºC
Dimensions (LxWxH)
430 x 250 x 360mm
Weight
19.5 kg
PRODUCT DESCRIPTION
PART NO.
*Standard HVA30
SH 0201
OPTIONAL ADD-ONS
TD 30 Tan Delta measurement system
SH 0207
PD 30 Partial Discharge system
SH 0220
Transport case
VKR 0002
Protective cover set
GH 0505
Vacuum bottle test fi rmware upgrade
(DC)
GH 0601
Discharge stick 60kV 1440R 9kJ
GH 0604
Special leads available in various
voltages, lengths, and connectors
GH 0501/2/3/4 and
GH 0506/20/21
The HVA30 is the most advanced HV test
system available, it is also the lightest,
most compact instrument of its type on the
market. The HVA30 has the highest power to weight ratio of any
comparable unit available.
There is no need to carry two pieces of equipment around and
then interconnect them!
Apart from the variable frequency VLF output, the operator can
also select dual polarity DC and cable jacket or sheath testing
output modes.
The applied test voltage, current, capacitance, resistance and
time are displayed and recorded.
The instrument is easily programmable allowing the operator
to setup or select test sequences in either automatic or manual
mode.
The HVA30 is capable of testing 0.5μF (Approx. 1500m /
5,000ft of cable) at 0.1Hz and 23kV rms. The frequency of the
output can also be reduced allowing even larger capacitance
•
•
•
•
•
loads to be tested. At 0.02Hz, approx. 7620m / 25,000ft of
cable can be tested.
To assist the operator, the instrument will automatically
calculate the optimum frequency to be selected for larger
loads.
The load independent, symmetrical output waveform avoids
the potentially destructive space charge effects caused by DC
polarization that occurs in aged extruded cables such as XLPE
/ PE / EPR, causing them to fail prematurely when exposed to
conventional high voltage DC or from a test instrument with
large non-symmetrical output waveforms.
Should a breakdown occur during testing, the actual voltage
at which it occurred is displayed and recorded. If cable burning
(fault conditioning) mode is activated, the fault resistance can
be conditioned to allow easier and less stressful fault location
techniques to be applied.
The results are stored in the instrument’s onboard memory
allowing easy retrieval and download to a PC or USB drive.
•
•
•
•
TECHNICAL DATA
DESIGN
ORDER CODES
HVA30 Test System
4.5m HV cable
Earth cable
USB memory stick
•
•
•
•
HVA Control Centre
Software
Operating manual
•
•
*STANDARD DELIVERY INCLUDES: