beautypg.com

Minuteman, Portable load bank, Model lpc-100) – Atec Avtron-LPC100 User Manual

Page 2: Specifications, Outline drawing

background image

16.25 [413.00]

25.75 [654.00]

10.25 [260.00]

RETRACTABLE

HANDLE

EXTENSION

WHEELS

TWIST DRAW LATCHES

30.25

[768.00]

21.33 [541.00]

1.50 [38.00]

10.98 [278.00]

AIR INTAKE SIDE

AIR EXHAUST SIDE

AIRFLOW

LOAD CONNECTION

CONNECTORS

CONTROL POWER

CONNECTOR

23.75

[603.00]

1.38 [35.00]

B15896

AVTRON

CAUTION

WARNING

DO

NOT

TILT

THIS

END

UP

REFER TO OWNERS MANUAL FOR SINGLE PHASE

LOAD CONNECTION AND METERING INSTRUCTIONS

WARNING: WHEN

OPERATING

SINGLE PHASE,

PROTECTIVE

PLUG MUST BE

INSTALLED IN

PHASE C

GND

A

B

C

KW LOAD STEPS

WARNING: LOAD CABLES MUST BE INSTALLED

AND LOCKED IN PLACE PRIOR TO CONNECTION

TO GENERATOR OR POWER SOURCE

LPC-100D LOAD BANK

MINUTEMAN

SPECIFICATIONS:

CONTROL POWER: The load bank requires control power of 120 VAC,

single phase, 60 Hz (line cord provided).

CONTROLS: The operator control panel includes a MASTER LOAD ON-

OFF switch, individual load step ON-OFF industrial toggle switches, a

CONTROL POWER ON-OFF switch, and a LOAD VOLTAGE selector switch.

COOLING: The resistive elements are air-cooled by eight high velocity

muffin fans.

LOAD CABLES: The load bank includes a 10' [3048] cable set with fully-

rated, quick-connect load terminals.

TRAVEL CASE: The load bank comes standard with a hard-shelf

protective travel case on casters with a telescoping handle.

DIGITAL METERING: Avtron Advanced Digital Monitor ing System

(ADMS)™ is provided for display of Volts, Amps, Frequency, and KW.

ADMS™ also includes Data Logging Software at no additional cost.

SAFETY FEATURES: The Minuteman Load Bank features multiple-array

overtemperature protection and wrong voltage detection circuitry. Load

Bus is short circuit protected by main line fuses (one for each phase).

WEIGHT:
Load Bank is approximately 78 lbs. [35 kg]

Load Bank, Case, & Cable Set is approximately 140 lbs. [63.5 kg]

Minuteman

Portable Load Bank

(Model LPC-100)

6255 Halle Drive • Cleveland, Ohio, U.S.A. 44125-4615 • 216.573.7600 • FAX 216.573.5953

www.avtronloadbank.com • [email protected]

Bulletin 440 • Rev. C

OUTLINE DRAWING:

LPC-100 RATINGS:
THREE PHASE

at 480 or 240 VAC

load steps are 12.5, 12.5, 25, 25, &

25 KW for a total of 100 KW
at 208 VAC

load steps are 10, 10, 20, 20, & 20 KW

for a total of 80 KW

SINGLE PHASE

at 120 VAC

load steps are 1.7, 1.7, 3.3, 3.3, &

3.3 KW for a total of 13.3 KW
at 240 VAC

load steps are 6.6, 6.6, 13.2, 13.2, &

13.2 KW for a total of 52.8 KW

ADMS™ is a trademark of Avtron LoadBank, Inc.

Communicator EXT™ is a trademark of Electro Industries/GaugeTech.

All dimensions are in inches [millimeters]. Specifications subject to change without notice.

Quality System Certified to ISO 9001