Minuteman, Portable load bank, Model lpc-100) – Atec Avtron-LPC100 User Manual
Page 2: Specifications, Outline drawing
16.25 [413.00]
25.75 [654.00]
10.25 [260.00]
RETRACTABLE
HANDLE
EXTENSION
WHEELS
TWIST DRAW LATCHES
30.25
[768.00]
21.33 [541.00]
1.50 [38.00]
10.98 [278.00]
AIR INTAKE SIDE
AIR EXHAUST SIDE
AIRFLOW
LOAD CONNECTION
CONNECTORS
CONTROL POWER
CONNECTOR
23.75
[603.00]
1.38 [35.00]
B15896
AVTRON
CAUTION
WARNING
DO
NOT
TILT
THIS
END
UP
REFER TO OWNERS MANUAL FOR SINGLE PHASE
LOAD CONNECTION AND METERING INSTRUCTIONS
WARNING: WHEN
OPERATING
SINGLE PHASE,
PROTECTIVE
PLUG MUST BE
INSTALLED IN
PHASE C
GND
A
B
C
KW LOAD STEPS
WARNING: LOAD CABLES MUST BE INSTALLED
AND LOCKED IN PLACE PRIOR TO CONNECTION
TO GENERATOR OR POWER SOURCE
LPC-100D LOAD BANK
MINUTEMAN
SPECIFICATIONS:
CONTROL POWER: The load bank requires control power of 120 VAC,
single phase, 60 Hz (line cord provided).
CONTROLS: The operator control panel includes a MASTER LOAD ON-
OFF switch, individual load step ON-OFF industrial toggle switches, a
CONTROL POWER ON-OFF switch, and a LOAD VOLTAGE selector switch.
COOLING: The resistive elements are air-cooled by eight high velocity
muffin fans.
LOAD CABLES: The load bank includes a 10' [3048] cable set with fully-
rated, quick-connect load terminals.
TRAVEL CASE: The load bank comes standard with a hard-shelf
protective travel case on casters with a telescoping handle.
DIGITAL METERING: Avtron Advanced Digital Monitor ing System
(ADMS)™ is provided for display of Volts, Amps, Frequency, and KW.
ADMS™ also includes Data Logging Software at no additional cost.
SAFETY FEATURES: The Minuteman Load Bank features multiple-array
overtemperature protection and wrong voltage detection circuitry. Load
Bus is short circuit protected by main line fuses (one for each phase).
WEIGHT:
Load Bank is approximately 78 lbs. [35 kg]
Load Bank, Case, & Cable Set is approximately 140 lbs. [63.5 kg]
Minuteman
Portable Load Bank
(Model LPC-100)
6255 Halle Drive • Cleveland, Ohio, U.S.A. 44125-4615 • 216.573.7600 • FAX 216.573.5953
www.avtronloadbank.com • [email protected]
Bulletin 440 • Rev. C
OUTLINE DRAWING:
LPC-100 RATINGS:
THREE PHASE
at 480 or 240 VAC
load steps are 12.5, 12.5, 25, 25, &
25 KW for a total of 100 KW
at 208 VAC
load steps are 10, 10, 20, 20, & 20 KW
for a total of 80 KW
SINGLE PHASE
at 120 VAC
load steps are 1.7, 1.7, 3.3, 3.3, &
3.3 KW for a total of 13.3 KW
at 240 VAC
load steps are 6.6, 6.6, 13.2, 13.2, &
13.2 KW for a total of 52.8 KW
ADMS™ is a trademark of Avtron LoadBank, Inc.
Communicator EXT™ is a trademark of Electro Industries/GaugeTech.
All dimensions are in inches [millimeters]. Specifications subject to change without notice.
Quality System Certified to ISO 9001