Atec Dranetz-PX5-400 User Manual
Px5-400, Ower, Plorer
PX5-400
P
OWER
X
PLORER
State-of-the-art monitoring of
50 /60 and 400 Hertz systems
in one instrument
Available Languages
Chinese, English, Finnish, French, German, Italian, Spanish, Swedish
General Specifications
Size (Hx W x D): 12" x 2.5" x 8" (30cm x 6.4cm x 20.3cm)
Weight: 4.2 pounds (1.9 kg)
Operating Temperature: 0º to 50º C (32º to 122º F)
Storage Temperature: -20º to 55º C (4º to 131º F)
Humidity: 10 to 90% non-condensing
System Time Clock-Crystal controlled-1 second resolution
Charger / Battery Eliminator: 90-264 VAC 47-63 Hz
Display: LCD color touch screen
Memory options (must have one): 32M-128M removable
compact flashcard
Optional Accessories
Current Probes: An extensive selection, including:
Model TR-2510A 0.1-10 A; up to 0.47" conductors
Model TR-2500A 10-500 A; up to 1/8" diameter
or 2.5" x 0.2"conductors
Model TR-2520A 300-3000 A; up to 2.56" diameter or
1.97" x 5.3" (bus bar)
Model TR-2019B 1-300 A; up to 2.0" conductors
(requires 116002-G1 adapter)
Flexible probes: ranging in current from 30-6000 A,
24", 36", 48"
Hall Effect Probes for AC/ DC applications, 150 A or 1500 A
CT Cable Adapter (CA4300LEM)
Voltage Cable Accessory Pack (VCP4300)
Soft Carrying Case (SCC-4300)
Field Replaceable Battery Pack (BP-PX5)
External Battery Charger (XBC-PX5)
Reusable Shipping Container (RSC-4300)
Weather resistant Container (ENCL-HH)
Lockable Portable Case (LPC-4300)
Communications Interface:
RS232 FiberOptic Adapter (COMM-RS232)
USB FiberOptic Adapter (COMM-OUA)
LAN-FiberOptic Adapter (COMM-OEA)
DRAN-VIEW software: Runs under Windows 98, ME, NT, XP
NodeLink
®
with download, setups and meter
CD-ROM Training Program
(1) PX5-400 samples at 32 samples/cycle, 1 cycle steps at 400 Hz.
Certain parameters measured at 45-65 Hz range only.
(2) Maximum harmonics to 16th at 400 Hz.
P
OWER
X
PLORER
PX5-400
dranetz-bmi.com
1.800.372.6832 [email protected]
tel 732.287.3680 • fax 732.248.1834 • 1000 New Durham Road • Edison, New Jersey 08818 USA
PowerXplorer, NodeLink and DRAN-VIEW are trademarks of Dranetz-BMI. ©2004 Dranetz-BMI. All rights reserved.
Printed in the United States. Specifications are subject to change without notice.
SPECIFICATIONS
Measured Parameters
(4) differential inputs, 1-600 Vrms, AC/DC, 0.1% rdg + 0.05% FS,
256 samples /cycle (1), 16 bit ADC
(4) inputs with CTs 1-6000 Arms CT-dependent, AC/ DC,
0.1% rdg + CTs, 256 samples/cycle (1), 16 bit ADC
1 MHz High Speed Sampling, 14 bit ADC
Frequency Range, 10 mHz resolution, 15-20 Hz, 45-65 Hz
or 350-450 Hz
Phase Lock Loop - Generator tracking, Standard PQ mode
Monitoring/Compliance
IEEE 1159
IEC 61000-4-30 Class A
MIL-STD-1399
Current Inrush / Energization
Voltage Fault Recording
Long Term Monitoring w/min/max/avg
Continuous Data Logging
Power Quality Triggers
Cycle-by-cycle analysis
256 samples /cycle; 1/ 2 cycle RMS steps (1)
L-L, L-N, N-G RMS Variations: Sags/swells/interruptions
RMS Recordings V & I (32 pre-fault, 10K post-fault cycles)
Waveshape Recordings (32 pre-fault, 10K post-fault cycles)
Low and Medium Frequency Transients - V & I
High Frequency Transients - V & I, 3% FS trigger
Harmonics Summary Parameters
Cross trigger V & I channels
RMS Event Characterization (IEEE or IEC)
Transient Event Characterization
Distortion/Power/Energy
W, VA, VAR, TPF, DPF, Demand, Energy, etc.
IEEE 1459 Parameters of distorted and unbalanced
Harmonics / Interharmonics per IEC 61000-4-7
THD/ Harmonic Spectrum ( V,I,W) to 63rd (2)
TID/Interharmonic Spectrum ( V,I) to 63rd (2)
Flicker per IEC 61000- 4-15 (Pst,Plt,Sliding Plt)
Crest Factor, K Factor, Transformer Derating Factor,
Telephone Interference Factor
Unbalance (max rms deviation) & sequencing components
5 User Spec Harmonics or Signaling Frequency
Vector/Arithmetic/Coincident Parameters
Power Quality Analyzer
www.dranetz-bmi.com