Atec Cincinnati-ZH Series User Manual
Page 3
Notes:
Performance is based on 230 volt, 60 Hz. operation and a 24°C ambient. If ambient temperature exceeds 30°C, CSZ recommends a water cooled
condenser. Some models available with increased performance/horsepower. The addition of certain options may affect chamber performance or
delivery time. The addition of live load will affect humidity control.
*Indicates Chambers with Tundra Refrigeration System. Specifications are subject to change.
Basic Specifications - Here’s what the Z-Series can do...
ELECTRICAL POWER REQUIREMENTS
PHYSICAL SPECIFICATIONS
FULL LOAD AMPERES
(INCHES/CM)
115 VOLT 208/230 VOLT 208/230 VOLT INTERIOR EXTERIOR
(±5%), (±5%), (±5%), WORKSPACE CABINET
MODEL 1 PHASE, 60 HZ 1 PHASE, 60 HZ 3 PHASE, 60 HZ WIDE DEEP HIGH WIDE DEEP HIGH
Z-2-.33-.33
16
-
-
20.5 / 52
12.5 / 32
13.75 / 35 28.5 / 72
34 / 86
46 / 117
ZH--2-.33-.33
16
-
-
20.5 / 52
12.5 / 32
13.75 / 35
34 / 86
34 / 86
46 / 117
Z-8-1
-
24
22
24 / 61
24 / 61
24 / 61
35 / 89
51 / 130
78 / 198
ZH-8-1
-
27
22
24 / 61
24 / 61
24 / 61
38 / 97
51 / 130
78 / 198
Z-8-1-1
-
33
23
24 / 61
24 / 61
24 / 61
35 / 89
51 / 130
78 / 198
ZH-8-1-1
-
35
26
24 / 61
24 / 61
24 /61
38 / 97
51 / 130
78 / 198
*Z-8-2
-
39
38
24 / 61
24 / 61
24 / 61
35 / 89
51 / 130
78 / 198
*ZH-8-2
42
38
24 / 61
24 / 61
24 / 61
38 / 97
51 / 130
78 / 198
Z-16-2
-
35
31
30 / 76
30 / 76
30 / 76
41 / 104
58 / 147
78 / 198
ZH-16-2
-
35
31
30 / 76
30 / 76
30 / 76
45 / 114
58 / 147
78 / 198
Z-16-2-2
-
51
39
30 / 76
30 / 76
30 / 76
41 / 104
58 / 147
78 / 198
ZH-16-2-2
-
51
39
30 / 76
30 / 76
30 / 76
45 / 114
58 / 147
78 / 198
*Z-16-3.5
-
50
46
30 / 76
30 / 76
30 / 76
41 / 104
58 / 147
78 / 198
*ZH-16-3.5
-
50
46
30 / 76
30 / 76
30 / 76
45 / 114
58 / 147
78 / 198
Z-32-2
-
35
31
38 / 97
38 / 97
38 / 97
49 / 124
66 / 168
78 / 198
ZH-32-2
-
35
31
38 / 97
38 / 97
38 / 97
53 / 135
66 / 168
78 / 198
Z-32-2-2
-
51
39
38 / 97
38 / 97
38 / 97
49 / 124
66 / 168
78 / 198
ZH-32-2-2
-
51
39
38 / 97
38 / 97
38 / 97
53 / 135
66 / 168
78 / 198
*Z-32-3.5
-
50
46
38 / 97
38 / 97
38 / 97
49 / 124
66 / 168
78 / 198
*ZH-32-3.5
-
50
46
38 / 97
38 / 97
38 / 97
53 / 135
66 / 168
78 / 198
COOLING PERFORMANCE
HEATING PERFORMANCE LIVE LOAD CAPACITY
WITH EMPTY CHAMBER
WITH EMPTY CHAMBER (WATTS)
Minutes from 24°C to:
24°C to -34°C -68°C
MODEL
-18°C -34°C -40°C -54°C -68°C
93°C 190°C to 24°C -18°C -34°C -40°C -54°C
Z(H)-2-.33-.33
-
-
25
35
65
30
60
20
30
-
-
200
150
Z(H)-8-1
20
40
-
-
-
10
25
10
-
650
225
-
-
Z(H)-8-1-1
-
-
25
35
55
10
25
10
15
-
-
650
450
*Z(H)-8-2
7
-
20
-
-
6
15
5
-
1800
-
725
-
Z(H)-16-2
10
20
-
-
-
15
35
10
-
1700
760
-
-
Z(H)-16-2-2
-
-
20
25
35
15
35
10
20
-
-
1500
1100
*Z(H)-16-3.5
6
-
15
-
-
8
20
6
-
3000
-
1300
-
Z(H)-32-2
15
30
-
-
-
20
55
10
-
1700
760
-
-
Z(H)-32-2-2
-
-
20
30
45
20
55
10
20
-
-
1500
1100
*Z(H)-32-3.5
10
-
25
-
-
12
30
8
-
3000
-
1300
-