Specifications

ELECTRICAL

Ranges

2Ω

20Ω

200Ω

2000Ω

20kΩ

Resolution

1mΩ

10mΩ

0.1Ω

1Ω

10Ω

Resistance Measurement
Frequency

128Hz square wave

Test Current

2mA, 10mA, 50mA

Accuracy

±2% of Reading ± 1ct from 10% to 100% of range

Auxiliary Electrode

Ry: 50kΩ on 20Ω, 200Ω, 2000Ω & 20kΩ ranges; 5kΩ on 2Ω range

Resistance

Rz: 2mA range: 15kΩ; 10mA range: 3000Ω; 50mA range: 400Ω

Interference

The unit is designed to reject high levels of interference voltages

at DC, or 50/60 Hz and their harmonics

Noise Influence

0.5% of range (max) to 20V peak

on Accuracy
Power Source

Built-in rechargeable 12V, one Ah NiCD battery, or external 12 V

DC

; low battery indication.

Battery can be recharged with built-in dual voltage charging unit:

94 to 127V or 187 to 253V (47 to 450Hz)

Charging Time

14 hours typical

Charging Supply Voltage

Internally selectable 110/220V, 45 to 450Hz

Battery Life

Four hrs on 50mA test current (800 15 sec measurements),

Seven hrs on 2mA and 10mA test currents (1500 15 sec. measurements)

Fuse Protection

500Vrms measurement circuit

MECHANICAL

Display

7-segment LCD, 0.71" (18mm) high (3

1

/

2

digit); 2000-count

Connection

Terminals accept spade lugs with min. gap of 6mm or

standard 4mm banana jacks

Operating Temperature

14° to 122°F (-10° to 50°C)

Dimensions

15.75 x 10.2 x 9.8" (400 x 260 x 250mm)

Weight

14 lbs (6.5kg) approximate

Case

Heavy-duty plastic, with detachable cover and carrying handle

Colors

Case: safety yellow; Front panel: brown

Dielectric Test

2000Vrms, 50/60Hz between 4 interconnected measuring terminals

and any external metal ground; 2000Vrms, 50/60Hz between line input

and measuring terminals on front panel

Environmental

O-ring sealed faceplate against water and dust; sealed cover

when closed; IEC529, DIN 0470-T1

SAFETY

Rating

EN 61010

Double Insulation

Yes

Impact Resistance

Shock and vibration according to MIL-T-28800D class 3

CE Mark

Yes

Features

Measures soil resistivvity (4-Point)

Measure ground resistance (2- and
3-Point) Fall-of-Potential Method

Step voltage tests and touch
potential measurements

Selectable: three test currents and
five resistance ranges

Measures very low resistance on
large grounding systems and grids

High test current also enables
geological surveys

Large easy-to-read LCD

Display includes indicators for excess
stray current and voltage, high
auxiliary rod resistance and fault
connection

Battery (rechargeable) powered or
external 12V

DC

Rugged dustproof and rainproof
field case

Can be used for continuity tests
on bonding

Includes power cord, 12V NiCD
battery, hex key, spare fuse and
user manual

Applications

Three-point measurement of large
grounding grids, counterpoises,
ground mats and grounded
equipment.

Soil resistivity tests (4-Point
measurement), commonly performed
by utilities at proposed construction

sites. Using soil resistivity analysis,
the size and complexity of grounding
system construction can be eval-
uated. The Ground Resistance Tester
Model 4500 will measure the resis-
tivity of epoxies, cement, ground
enhancement materials and many
other substances.

Step or touch potential levels under
true fault conditions can be deter-
mined by using the Model 4500 to
inject a simulated low-level fault into
an electrical system. When used in
this fashion, the Model 4500 will
display readings in volts per fault
ampere.

Two-point tests for continuity tests
on bonding or on pre-established
grounds.