Det2/2 auto earth tester ordering information, Specifications – Atec Biddle-DET-2-2 User Manual
Page 2
DET2/2
Auto Earth Tester
ORDERING INFORMATION
Item (Qty)
OrderCode.
Auto Earth Tester
DET2/2
Included Accessories
Mains supply lead for battery charging
Operating instruction book
6171-728
Optional Accessories
Earth testing kit
6310-755
Comprising carrying case and pouch containing:
Four galvanised steel spikes (‘L’ shape) 10 mm dia. (0.4 in. dia.
approx) x 350 mm (14 in. approx) long
30 m (98,5 ft approx) of cable on a winder
50 m (164 ft approx) of cable on a winder
Two 3 m leads complete with connectors and clips
Hammer
Reel of cable, 50 m [164 ft. approx]
6121-119
Resistivity tests assist in the design of a correct earth
system and avoid the cost of re-working electrode
installations.
Earth testing kits, which include suitable test spikes and
test leads, are available separately.
specifications
Earth Resistance Range
0,010
Ω to 19,99 kΩ (auto-ranging),
1 m
Ω resolution.
Accuracy (23°C ±2°C)
±0,5% of reading ±2 digits
Service Error
±5% of reading ±2 digits ±10 m
Ω (meets
VDE service error over 50 m
Ω)
Comply with Standards
BS 7430 (1991)
VDE 0413 Part 7 (1982)
Test Frequency
105 to 160 Hz reversing d.c. (50 Hz operation default to 128 Hz,
60 Hz operation default to 150 Hz) Set in steps of 0,5 Hz
Test Current
50 mA max (selectable high and low levels)
Maximum Output Voltage
< 50 V r.m.s.
Maximum Interference
Typically 40 V peak-to-peak (50/60 Hz, sinusoidal nature)
Display
Alphanumeric L.C.D. (130 x 35 mm) giving test information and a
large (20 mm) 3
1
⁄
2
-digit reading)
Temperature Coefficient
< ±0.1% per °C over the temperature range -10 to +40°C
0,05% per °F from 14 to 104°F
Temperature Range
Operating:
-10 to +40°C (14 to 104°F)
Storage:
-20 to +60°C (-4 to +140°F)
Humidity
Operating: 90% RH max. at 40°C (104°F)
Environmental Protection
The instrument is waterproof to IP54
Flash Test: 3 kV a.c.
Voltage Withstand
In the event of a system fault, the instrument will withstand
240 V a.c. applied between any two terminals.
Power Supply
Internal
Rechargeable, sealed lead-acid battery.
12 V (nominal), 2,6-Ah capacity.
Battery voltage over which basic accuracy is maintained is 11,0 to
13,5 V.
Battery life: Approximately 5 hrs. continuous use.
Battery charging time: 6 hrs. max. (from completely
exhausted), charging current automatically controlled to stop
over-charging.
Charging supply required: 100 to 130 V or 200 to 260 V,
50/60 Hz.
Power consumption: 9 W max. at 12 V.
Safety
The instruments meet the requirements of IEC61010-1.
EMC
In accordance with IEC 61326 -1.
Dimensions:
245 H x 344 W x 158 D mm
(9,6 H x 13,5 W x 6,25 D in. approx.)
Weight:
5 kg (11 lb approx.)
Maximum Current Spike (Loop) Resistance
High
Low
Range
Current
Current
(RE )
(RC )
(RC )
0,010 to 0,499
Ω
5 k
Ω
1 k
Ω
0,500 to 1,999
Ω
5 k
Ω
3 k
Ω
2,000 to 19,99
Ω
10 k
Ω
5 k
Ω
(over 20
Ω RC > 20 kΩ)
Maximum Potential Spike (Loop) Resistance
High
Low
Range
Current
Current
(RE )
(RP )
(RP )
0,010 to 0,499
Ω
11 k
Ω
11 k
Ω
0,500 to 1,999
Ω
21 k
Ω
11 k
Ω
2,000 to 19,99
Ω
21 k
Ω
11 k
Ω
(over 20
Ω RP > 20 kΩ)
UK
Archcliffe Road Dover
CT17 9EN England
T +44 (0) 1304 502101
F +44 (0) 1304 207342
UNITED STATES
4271 Bronze Way
Dallas TX 75237-1088 USA
T 800 723 2861 (USA only)
T +1 214 333 3201
F +1 214 331 7399
OTHER TECHNICAL SALES OFFICES
Norristown USA, Toronto CANADA,
Mumbai INDIA, Trappes FRANCE,
Sydney AUSTRALIA, Madrid SPAIN
and the Kingdom of BAHRAIN.
Registered to ISO 9001:2000 Reg no. Q 09290
Registered to ISO 14001 Reg no. EMS 61597
DET2_2_DS_en_V12
www.megger.com
Megger is a registered trademark