Tdr9000, Introduction, Benefits – Atec Doble-TDR9000 User Manual
Page 2: Description
TDR9000
Introduction
The TDR9000 Circuit Breaker Test System provides efficient, accurate measure-
ments of circuit breaker dynamic timing and motion.
Field proven for over 25 years, more than 2,300 Doble circuit breaker diagnos-
tic instruments have been sold.
Benefits
• Accurate measurement of grading capacitors capacitance values, and
insertion resistor resistance values –
built-in, precision measurements
for grading capacitors and insertion resistors testing eliminates the need
for separate measuring instruments. No other product on the market can
match the TDR9000 in this capability.
• Immune to Interference – accuracy of test results is unaffected
by severe conditions of electrostatic and electromagnetic inter-
ference, present in harsh substation environments.
• Modular Design – customize the system to match present
testing requirements; field upgrade the system as required,
to protect the capital investment.
• High Accuracy Motion Recording – a patented digital rotary
and linear transducer provides early diagnosis of mechanical
problems, auxiliary switch and main contact timing errors.
• Rugged and Reliable – the TDR9000 is a single box solution,
providing the accuracy of a laboratory instrument with
durability for field use.
• Self-Diagnostics – self-diagnostics on demand ensures accurate
and valid test results.
• User-friendly PC interface – an intuitive control panel on
your PC provides quick, efficient and simple testing of circuit
breakers.
• Comprehensive Testing – accurately measures all essential
parameters of a circuit breaker in a single test for accurate
diagnostics of the circuit breaker operation.
Description
The TDR9000 is a state-of-the art Circuit Breaker Test System
engineered to test all types of circuit breakers. The modular con-
struction of the TDR9000 allows testing of simple circuit breakers,
to very complex circuit breakers, using a single, field-portable and
rugged instrument. The modular design allows users to acquire a
Circuit Breaker Test System matched to today’s specific testing
applications and permits easy upgrades in the field to expand the
capabilities to test different or more complex apparatus. The mod-
ular design results in complete usage of its capital investment and
simultaneously provides an upgrade path to test future circuit
breaker designs.
Packaged in a compact, portable and sturdy case, the TDR9000 is
the singlebox solution for Circuit Breaker Testing in the field.
The TDR9000 provides testing of up to eight breaks per phase,
for a total of 24 main contacts simultaneously. The EHV The
Breaker Performance Report
TDR9000 Version: RE 4.01
Manufacturer :A.B.C. Electric
Location
: Webster Circuit
Model Number: 1234-GW-10000
Circuit
: 45678
Serial Number : 1-38Y1740
Operator
: You
Instr Book # : 33-123-C3
Mechanism #
:
Mech Instr # :
Special ID : 02472
Operation Counter
: 696
:
:
Test Type
: TRIP
Test Plan Name
:
Test was performed on 03/30/2004 at 13:09:10.
Motion Channels 1-3 Transfer Function
1.000 in Travel at the contacts is 1.000 in Travel at the transducer.
Command Parameters
Trip Pulse
4.00 cy
Close Pulse
95.50 cy
Delay 1
0.50 cy
(Standing)
Command Currents
Trip Current
16.55 A pk
Close Current 0.72 A pk
Identification
Test Tabulation
OCB Contact Timing
Reclose Operation
Reclose Dead Time Within a Phase
Specifications
Test Results
Compare
Maximum 16.50 cy
Minimum
Phase A 16.92 cy
Phase B 16.81
Phase C 16.72
Fail
Fail
Fail
Reclose Dead Time Within the Breaker
Specification
Test Results
Compare
Breaker 16.72 cy
Fail
Main Contact Opening Time Measured From Test Initiation
Specifications
Test Results
Travel
Velocity
Compare
Maximum 1.90 cy
Minimum 0.00
CONTACT1 1.51 cy
CONTACT2 1.60
CONTACT3 1.68
0.48
in
0.68
0.84
8.84
ft/s
9.50
11.40
Pass
Pass
Pass
Delta Main Contact Opening Time Within the Breaker
Specifications
Test results
Compare
Maximum 0.30 cy
Breaker 0.17 cy
Pass
Main Contact Reclosing Time Measured From Test Initiation
Specifications
Test Results
Travel
Velocity
Compare
Maximum 20.00 cy
Minimum 16.00
CONTACT1 18.43 cy
CONTACT2 18.41
CONTACT3 18.40
0.52 in
0.50
0.47
7.40 ft/s
7.30
7.08
Pass
Pass
Pass
Delta Main Contact Reclosing Time Within the Breaker
Specifications
Test results
Compare
Maximum 0.30 cy
Breaker 0.03 cy
Pass
Specifications
Test results
Compare
Average Velocity in Open zone 1
Maximum 16.00 ft/s
Minimum 14.00
Zone 1 1.000 in to 5.000 in
VEL 1. 14.84 ft/s
Pass