F6300 APPliCAtion eXAmPle AnD DeSCriPtion

The F6300 and F6150 combination can easily test all high-burden electromechanical
relays. The burden presented by electromechanical relay-based protection schemes are
very high, requiring high-power current sources to drive the necessary current. When
used together, the F6300 and F6150 can deliver three currents up to 90 A, 3-phase
continuous at 450 VA or 180 A for 1.5 seconds at 675 VA.
Three voltage sources and one current source of 450 VA are provided by the F6150,
while two 450 VA current sources are provided by the F6300.

AC Amplitude Accuracy at 50/60 Hz
Current Sources

From 20° to 30° C: < 0.02% typical or
< 0.09%
Guaranteed typical 0.02% of reading

Distortion and noise at 50/60 Hz output
(10 Hz-2 kHz Bandwidth)
Current Sources

Total Harmonic Distortion (THD) < 0.02%
typical, < 0.1% guaranteed

Phase Angle:

range:

0 to + 359.9° (lead) /
0 to – 359.9° (lag)

Accuracy:

±0.25° at 50/60 Hz for
current sources

resolution:

0.1°

Frequency:

Bandwidth:

dc to 3 kHz at full
power for transient play-
back

range:

dc; ac from 0.1 Hz to

2 kHz at full power

continuous load

resolution:

0.001 Hz

Accuracy:

0.05 ppm

Typical

1.5 ppm

20° to 30° C

10 ppm

0° to 50° C

toget

Her

we

P

ower

t

He

worl

D

Doble Engineering Company
85 Walnut Street
Watertown, MA 02472 USA
tel +1 617 926 4900
fax +1 617 926 0528

MKT-SL-F6300-03/08

Doble is certified iSo 9001:2000

Doble is an eSCo technologies Company

F6300 technical Specifications and Source
Configurations

output Power Continuous
2 x 450 VA sources
6 x 150 VA sources
output Power transient for 1.5 seconds
2 x 675 VA sources
6 x 225 VA sources

2 x 450 VA Sources
ranges (resolutions)
AC Current

1.5 seconds transient 15A (0.001 A), 45,
90, 180 A rms (0.01 A)
Continuous 7.5 (0.001 A), 22.5 A, 45,
90 A rms (0.01 A)

DC Current

1.5 seconds Transient 10 (0.001 A), 30,
60, 120 A dc (0.01A)
Continuous 5 15 (0.001 A), 30, 60 A dc
(0.001 A)

6 x 150 VA Sources
ranges (resolutions)
AC Current

1.5 seconds Transient 15 (0.001 A), 30,
60 A rms (0.01 A)
Continuous 7.5, 15 A (0.001 A), 30 A rms
(0.01 A)

DC Current

1.5 seconds Transient 10 (0.001 A), 20,
40 A dc (0.01 A)
Continuous 5 A (0.001 A), 10, 20 A dc
(0.01 A)

Physical Specifications

Dimensions:

15 x 9.5 x 18 inches
38 x 24 x 45.7 cm

weight:

35.4 lb / 16.1 kg


line Power Supply: 105–132 V or 210–264

V, 47–63 Hz

interfaces:

RS 232 and Ethernet
control to PC

operating
temperature:

0° to 50° C
32° to 122° F

Storage
temperature:

-25°to 70° C
-13° to 158° F

Humidity:

Up to 95% relative hu-
midity, non-condensing

Specifications are subject to change without