beautypg.com

Specifications – Atec AEMC-3711-3731 User Manual

Page 4

background image

Models 3711 & 3731 (pdf)

08/02

Technical Assistance (800) 343-1391

www.aemc.com

4 of 7

Specifications

ELECTRICAL

Ground Resistance Ranges

Auto-Ranging 0.01

to 1200

Range

0.10 to

1.0 to

50.0 to

100 to

200 to

400 to

600 to

1.00

50.0

100.0

200

400

600

1200

Resolution

0.01

0.1

0.5

1

5

10

50

Accuracy

±2%

±1.5%

±2%

±3%

±6%

±10%

Approx. 25%

of Reading

of Reading

of Reading

of Reading

of Reading

of Reading

of Reading

± 0.02

± 0.1

± 0.5

± 1

± 10

± 10

± 50

Current Measurement Ranges

Auto-Ranging 1mA to 30.00Arms

Range

1 to 299mA

0.300 to 2.999A

3.00 to 29.99A

Resolution

1mA

0.001A

0.01A

Accuracy

±2.5% of Reading + 2mA

±2.5% of Reading + 2mA

±2.5% of Reading + 20mA

Resistance Measurement
Frequency

2403Hz

Resistance Overload

OL displayed above 1200

Current Measurement
Frequency

47 to 800Hz

Current Overload

OL displayed above 29.99Arms

Power Source

9V Alkaline battery (IEC 6LF22 or NEDA 1604A)

Battery Life

Typical: 8 hours or approx. 1000 measurements of 30 seconds

MECHANICAL

Display

3

3

/

4

Digit, 1.73 x 1.10" (44 x 28mm)

Operating Temperature

14° to 131°F (-10° to 55°C)

Storage Temperature

-22° to 158°F (-30° to 70°C)

Relative Humidity

10 to 90% RH @ 14° to 104°F (-10° to 40°C), 75% RH @ 131°F (55°C)

Dimensions

9.25 x 3.94 x 2.17" (235 x 100 x 55mm)

Weight

2.2 lbs (1kg)

Jaw Window Diameter

1.25" (32mm)

Jaw Opening

1.38" (35mm)

Case

Lexan

®

920A or equivalent (UL94V2)

Colors

Gray body, red jaws

Shock Test

IEC 68-2-27

Vibration Test

IEC 68-2-6

6

Drop Test (1m)

IEC 68-2-32

Dielectric Test

2500V

AC

Environmental

IP30, IEC 359, Group III

Working Voltage

150V, Cat. III – Pollution Degree 2; 300V, Cat. II – Pollution Degree 2

Max Overload (A or

Function)

100A continuous, 200A (< 5s) 50/60Hz

U.S. Patent

No. 362,639

UL File No.

E192383

SAFETY

Safety Rating

EN 61010-2-032 (Class 2) Double Insulation

CE Mark

Yes