beautypg.com

Atec Biddle-651028 User Manual

Page 3

background image

BIDDLE IMPULSE GENERATORS

SPECIFICATIONS

Max. Stored

Storage

Impulse

Output Ranges

Model

Cat. No.

Energy

Capacitance

Interval

Impulse

Proof Test Burn Current Weight

15-kV

651017

563 Joules

5

µ

F

Variable

0 to 15 kV

0 to 25 kV

0 to 30 mA

75 lb

Portable

1 to 5 s

(34 kg)

Dual-Voltage

651016

450 Joules

16

µ

F

8 s

0 to 7.5 kV

0 to 25 kV

0 to 30 mA

80 lb

4

µ

F

(36 kg)

Standard

651028

1250 Joules

4

µ

F

6 s @ 60 Hz

0 to 25 kV

0 to 30 kV

0 to 50 mA

195 lb

7.2 s @ 50 Hz

(88 kg)

653031

3750 Joules

12

µ

F

5 s @ 60 Hz

0 to 25 kV

0 to 65 kV

0 to 100 mA

750 lb

Heavy-Duty

5400 Joules*

12

µ

F

6 s @ 50 Hz

0 to 30 kV

(340 kg)

653031-32

7500 Joules

24

µ

F

10 s @ 60 Hz

0 to 25 kV

0 to 65 kV

0 to 100 mA

770 lb

10,800 Joules*

24

µ

F

12 s @ 50 Hz

0 to 30 kV

(349 kg)

*Intermittent

• The 65 kV proof mode permits ac-
ceptance testing of 15 kV class cable
and maintenance testing of 25 kV class
cable.

• The 65 kV/100 mA burn mode per-
mits simple breakdown testing and
fault resistance reduction to locate
faults on 35 kV class cable.

This unit offers the following power
output capabilities:

• It delivers 3750 Joules with 12

µ

F at

25 kV every 5 seconds, with an
overrange that permits a maximum
discharge of 5400 Joules at 30 kV inter-
mittently.

• Optionally, it delivers 7500 Joules
with 24

µ

F at 25 kV every 10 seconds,

with an overrange that permits a maxi-
mum discharge of 10,800 Joules at 30
kV intermittently.

Heavy-duty model, cat. no. 653031

SPECIFICATIONS

Input Power

15-kV Portable and Dual-Voltage

Models: Nominal 120 Vac, 4.5 A, 1-

φ

,

50/60 Hz

Standard Model: Nominal 120 Vac, 9 A,

1-

φ

, 60 Hz

Heavy-Duty Model: Nominal 120 Vac,

25 A, 3 kVA, 60 Hz.

To order instrument with input other
than noted above, add one of the follow-
ing to Catalog No.:

-43

Nominal 120 Vac, 50 Hz

-44

Nominal 220 Vac, 60 Hz

-45

Nominal 220 Vac, 50 Hz

-46

Nominal 240 Vac, 60 Hz

-47

Nominal 240 Vac, 50 Hz

Cables Supplied

One permanently connected shielded
output cable for coaxial high voltage
and return leads; one ground cable,
and one permanently connected input
cord. Lengths shown below.

Dimensions

15-kV Portable Model

27 L x 13.5 W x 13.5 H in.
(690 L x 343 W x 343 W mm)

Dual-Voltage Model

13.5 L x 13.5 W x 24 H in.
(243 L x 343 W x 610 W mm)

Standard Model

16 L x 16 W x 34 H in.
(406 L x 406 W x 364 H mm)

Heavy-Duty Model

36 L x 24 W x 40 H in.
(914 L x 610 W x 1016 H mm)

Environmental

Temperature

Operating: 14 to 113

o

F (-10 to +45

o

C)

Storage: -22 to +131

o

F (-30 to +55

o

C)

Elevation

7500 ft (2286 m) maximum. Derate
voltage at higher altitudes.

Humidity

5 to 95% RH noncondensing.

Climate

Operation in direct rain or snow is
prohibited.

Cable Length

Model

Output

Ground

Input

15-kV Portable and

25 ft (7.6 m)

15 ft (4.5 m)

15 ft (4.5 m)

Dual-Voltage

Standard

50 ft (15.2 m)

25 ft (7.6 m)

25 ft (7.6 m)

Heavy-Duty

150 ft (45.6 m)

50 ft (15.2 m)