Features, Applications, Specifications – Atec Aemc-5600 User Manual
Page 2
![background image](/manuals/318064/2/background.png)
Digital Micro-Ohmmeter Model 5600 (pdf)
03/03
Technical Assistance (800) 343-1391
2 of 5
Specifications
ELECTRICAL
Range
2000µ
Ω
20m
Ω
200m
Ω
2000m
Ω
20
Ω
200
Ω
Display
1999
19.99
199.9
1999
19.99
199.9
Resolution
1µ
Ω
10µ
Ω
100µ
Ω
1m
Ω
10m
Ω
100m
Ω
Test Current
10A
1A
1A
100mA
10mA
10mA
Accuracy
0.25% typical
0.25% typical
0.25% typical
0.25% typical
0.25% typical
0.25% typical
0.5% max ± 2cts 0.5% max ± 1ct 0.5% max ± 1ct 0.5% max ± 1ct 0.5% max ± 1ct 0.5% max ± 1ct
Power Source
Rechargeable 6V, 7Ah NiCD battery; built-in 110V/220V (47 to 450Hz) charger;
automatic shutoff after 4 minutes non-use
Battery Life
200µ
Ω
range: 200 to 300 8-second measurements
20-200m
Ω
ranges: 900 30-second measurements (approx.)
2000m
Ω
, 20-200
Ω
ranges: 5000 30-second measurements (approx.)
Operating Voltage
4.5 to 7V
DC
Recharge Time
14 hours from full discharge (approx.)
MECHANICAL
Display
2000-count, 7-segment LED
Connection
Terminals accept 4mm banana plugs or 6mm (min) spade lugs
Operating Temperature
14° to 131°F (-10° to 55°C)
Storage Temperature
-4° to 131°F (-20° to 55°C)
Dimensions
15.35 x 10.24 x 9.84" (390 x 260 x 250mm)
Weight
17 lbs 10 oz (8kg)
Case
Fiberglass-charged polycarbonate with handle and removable lid,
watertight to IP534 (lid closed), IP520 (lid open)
Colors
Safety-yellow case, gray faceplate
SAFETY
Safety Ratings
Electrical: IEC 38, Supply voltage, Electromagnetic: IEC 801-2, Electrostatic discharge;
EN 61010, 300V, Cat. II, IEC 801-3, Electromagnetic fields; IEC 801-5, Electrical shocks,
Mechanical/environmental: IEC 529, Protection Index (IP); IEC 68.2.6, Vibration;
IEC 68.2.27, Shocks; IEC 68-2-29, Shake IEC 68.2.31, Knock over;
IEC 68.2.32, Drop test, Case Material: UL94
Overload Input Protection
380Vrms
Fuses
Two high-interrupting capacity 8A 380V, 1
1
/
4
x
1
/
4"
CE Mark
Yes
Features
•
Four-terminal Kelvin resistance
measurement
•
Up to 10A test current
•
0.25% basic accuracy
•
1m
Ω
resolution
•
Direct reading, easy to operate
•
Six selectable ranges
•
Reverse polarity switch
•
Overload and input fuse protection
•
Automatic decimal point and zero
•
Rechargeable NiCD battery with
integral charger (110/220V)
•
Rugged field case for industrial
applications
Applications
•
Contact resistance of breakers
and switches
•
Wire to terminal connections
•
Winding resistance of motors
and transformers
•
Resistance on electric motors
•
Aircraft and rail bonds
•
Grounding connections
•
Battery strap measurements
Test Equipment Depot www.testequipmentdepot.com
99 Washington Street 800-517-8431
Melrose, MA 02176-6024 781-665-0780 FAX