Alpha Technologies MiniMax Power Supply User Manual
Page 10

3. Installation
10
164201241-001 Rev. C0
2.
Remove all equipment, hardware, and options from the cabinet and store in a
secure location for future use.
3.
Remove the U-shaped mounting bracket from the cabinet rear panel.
4.
Use the bracket as a template to mark mounting holes at the desired mounting
location. If possible, position the cabinet so the front panel is easily accessible.
5.
Drill 11/16" holes in the pole at the marked locations.
6.
Attach the mounting bracket to the pole using customer-supplied hardware. Tighten
securely.
7.
Optional metal band mounting for metal/cement poles: insert the customer-supplied
metal bands or straps through the band slots on the mounting bracket. Tighten the
bands securely.
8.
Raise the cabinet and set into place on the bracket. Attach the cabinet using the
hardware removed in Step 2. Tighten the bolts securely.
9.
Confirm availability of a suitable ground rod next to the power pole. If required, drive
a rod according to local codes.
10. Continue to “Electrical Connections”.
3.1
Pole Mounting
(Models PSF-MXP-*** and PCS-MXP-***)
,
continued
- AlphaCell GelCell Series (32 pages)
- FXM 650, 1100, 2000 UPS (96 pages)
- Cordex 48-1.2kW (68 pages)
- Radium MiniBay (57 pages)
- Fiber Backhaul Enclosure (FBE) (19 pages)
- FBE2322 Enclosure System (38 pages)
- FlexNet PMR, GMR Series (49 pages)
- Te25xh (38 pages)
- FlexNet MPS48-12M - Technical Manual (33 pages)
- FlexNet MPS48-12M - Quick Start Guide (2 pages)
- FlexNet ELPM 300-48D (25 pages)
- FlexNet FMPS (40 pages)
- FlexPoint AX Series (34 pages)
- FlexPoint FPR1207-F - Technical Manual (18 pages)
- FlexPoint FPR1207-F - Quick Start Guide (2 pages)
- AlphaGen PN-6x-T 7.5kW 48VDC - Installation and Operation Manual (79 pages)
- AlphaGen CE-3x2 5K-T 48Vdc (95 pages)
- AlphaGen PN-6x-T 7.5kW 48Vdc (95 pages)
- AlphaGen 3.5_5.0kW Kohler COM5 (80 pages)
- Security Bar Field For UPE-3, UPE-6, UPE-M3, UPE-M6, PN Series and CE Series (2 pages)
- AMPS80 HP (116 pages)
- 255A Bypass Switch (24 pages)
- AMP24 HP (108 pages)
- FXM350_Micro350 UPS (112 pages)
- CFR 600, CFR 600XT, CFR 1000 (70 pages)
- BPS Series Bypass Switch (36 pages)
- CFR Intelligent Interface Device (54 pages)
- CFR Redundant Control Unit (23 pages)
- CFR 5000, CFR 5000RM (88 pages)
- CFR 3000, CFR 3000RM (86 pages)
- CFR 1500, CFR 1500RM (83 pages)
- CFR 1500, CFR 2000, CFR 2500, CFR 3000 (76 pages)
- Continuity: 1000_2000_3000 (48 pages)
- Continuity Battery Pack (20 pages)
- Continuity: 6K_10K (52 pages)
- Micro, Micro XL, Micro XL3 UPS (99 pages)
- Micro Secure UPS (80 pages)
- Te17 (32 pages)
- Te45 (68 pages)
- Te41, 48V (76 pages)
- Te41, 24V (72 pages)
- Te43 (60 pages)
- AlphaGuard AG-CMT Installation (2 pages)
- AlphaGuard AG-CMT-3SC_4SC-P (2 pages)
- Digital Midtron DM-3200 AT (2 pages)