8 service power inserter, Installation – Alpha Technologies CESC User Manual
Page 20
![background image](/manuals/317446/20/background.png)
2.8
Service Power Inserter
1.
The SPI box(es) are mounted on the shelf
support bracket.
2.
Remove the two screws on the face of the
SPI and lift off the cover to gain access to
the Seizure Screw Assembly. Loosen the
seizure Screw several turns so that the
stinger will pass through the clamp. (Fig 2-3)
3,
Insert the Coaxial Termination into the output
port on the bottom of the SPI. Ensure that
the stinger goes through the Seizure Screw
Assembly. Tighten the Coaxial Termination.
4.
Tighten the seizure screw to 35.0 Inch-Pounds.
Replace the SPI cover and screws.
Ensure that the switch on the top or the SPI is
in the ON position, the AUX position is used
only when an alternate power source is
connected to the SPI.
Seizure Screw
Assembly
Coax
Termination
Seizure
Screw
Coax
Stinger
2. Installation
20
031-106-C1-001 Rev. A
Fig. 13 Location of SPI
Fig. 12 Cable Connection
Fig. 11 Seizure Screw Assembly Location
- AlphaCell GelCell Series (32 pages)
- FXM 650, 1100, 2000 UPS (96 pages)
- Cordex 48-1.2kW (68 pages)
- Radium MiniBay (57 pages)
- Fiber Backhaul Enclosure (FBE) (19 pages)
- FBE2322 Enclosure System (38 pages)
- FlexNet PMR, GMR Series (49 pages)
- Te25xh (38 pages)
- FlexNet MPS48-12M - Technical Manual (33 pages)
- FlexNet MPS48-12M - Quick Start Guide (2 pages)
- FlexNet ELPM 300-48D (25 pages)
- FlexNet FMPS (40 pages)
- FlexPoint AX Series (34 pages)
- FlexPoint FPR1207-F - Technical Manual (18 pages)
- FlexPoint FPR1207-F - Quick Start Guide (2 pages)
- AlphaGen PN-6x-T 7.5kW 48VDC - Installation and Operation Manual (79 pages)
- AlphaGen CE-3x2 5K-T 48Vdc (95 pages)
- AlphaGen PN-6x-T 7.5kW 48Vdc (95 pages)
- AlphaGen 3.5_5.0kW Kohler COM5 (80 pages)
- Security Bar Field For UPE-3, UPE-6, UPE-M3, UPE-M6, PN Series and CE Series (2 pages)
- AMPS80 HP (116 pages)
- 255A Bypass Switch (24 pages)
- AMP24 HP (108 pages)
- FXM350_Micro350 UPS (112 pages)
- CFR 600, CFR 600XT, CFR 1000 (70 pages)
- BPS Series Bypass Switch (36 pages)
- CFR Intelligent Interface Device (54 pages)
- CFR Redundant Control Unit (23 pages)
- CFR 5000, CFR 5000RM (88 pages)
- CFR 3000, CFR 3000RM (86 pages)
- CFR 1500, CFR 1500RM (83 pages)
- CFR 1500, CFR 2000, CFR 2500, CFR 3000 (76 pages)
- Continuity: 1000_2000_3000 (48 pages)
- Continuity Battery Pack (20 pages)
- Continuity: 6K_10K (52 pages)
- Micro, Micro XL, Micro XL3 UPS (99 pages)
- Micro Secure UPS (80 pages)
- Te17 (32 pages)
- Te45 (68 pages)
- Te41, 48V (76 pages)
- Te41, 24V (72 pages)
- Te43 (60 pages)
- AlphaGuard AG-CMT Installation (2 pages)
- AlphaGuard AG-CMT-3SC_4SC-P (2 pages)
- Digital Midtron DM-3200 AT (2 pages)