3.4 Air Cleaner Service
Do not use gasoline or low flash point solvents for cleaning. They are flammable and explosive
under certain conditions.
WARNING! FIRE HAZARD
Never run the generator without the air cleaner, otherwise rapid engine wear may result.
CAUTION!
A dirty air cleaner will restrict air flow to the carburetor. To prevent carburetor malfunction, service the air
cleaner regularly. Service more frequently when operating the generator in extremely dirty areas.
Tools Required:
#2 Philips Head Screwdriver
Procedure:
1. Remove the maintenance cover.
2. Remove three air filter retaining screws. Remove the air cleaner cover and check the air cleaner
element. Clean or replace the element if necessary.
3. Wash the element in a non-flammable or high flash point solvent and dry it thoroughly.
4. Soak the element in clean engine oil and squeeze out the excess oil.
5. Reinstall the air cleaner element and the air cleaner cover. Tighten the cover screws securely.
6. Reinstall the maintenance cover and tighten the screws securely.
Fig. 3-3, Air Cleaner Assembly
Captive Screw
Maintenance
Cover
Air Cleaner
Cover
Air Cleaner
Element
Air Cleaner
Case
3.0
Servicing, continued