0 specifi cations, Hardware, Environmental – Alpha Technologies IDH3 User Manual
Page 26: Rf transmit/receive, Power supply monitored parameters, Generator monitored parameters
![background image](/manuals/317411/26/background.png)
26
745-420-B0-001 Rev. A
Power Supplies Supported:
XM2-HP, XM2
DOCSIS Compatibility:
DOCSIS 1.1, 2.0
Monitoring Protocol:
SNMP v1
Devices Monitored:
Power Supply, Batteries and Generator
(compatible with ANSI/SCTE 25-3 2002,
formerly HMS 022)
Hardware
RF Cable Interface:
F-connector, female, 75Ohm
Local Interface:
Ethernet interface for direct web page
access to diagnostic information.
LED Indicators:
Transponder Ready/RF Link Established
Transponder/CMTS Communications
Power Supply/Transponder
Communication
Environmental
Operating Temperature:
-40 to 65°C / -40 to 149°F
Humidity:
10 to 90% non-condensing
Emissions:
EN50022 Class A and FCC Part 15
Class A
(Installed in power supply enclosure
system)
RF Transmit/Receive
Tx Frequency Range:
5 to 42MHz
Output Power:
8 to 58dBmV
Channel Bandwidth:
6MHz
Receive Center
Frequency Range:
91 to 857MHz (Standard, HRC, IRC
channels)
Input Level:
-15 to 15dBmV
5.0 Specifi cations
Power Supply Monitored Parameters
Major Alarm:
Logical (OR) of: test fail, battery fail, line
isolation alarm, output overload, inverter
over temperature, N+1 active, fuse fail
Minor Alarm:
Logical (OR) of: temperature probe error,
AC line loss, N+1 error
Input Line Voltage:
90 to 270Vac 50/60Hz measured value
Output Voltage:
60/90Vac measured value
Output Current 1:
0 to 25A measured value
Output Current 2, 3, 4:
0 to 25A measured value (if optional ports
installed)
Output Power:
Calculated, reported in AC Watts
UPS Status:
AC line, Standby, Test in-process, Test
alarm
Enclosure Door:
Open/Closed
Battery Voltage:
6 or 12V batteries, up to 4 battery strings
Individual battery voltages measured
reported to ±100mv resolution
Battery Temperature:
Measured, reported in Celsius
Remote Test Control:
Start/Stop XM2 self test cycle
Generator Monitored Parameters
Status:
Engine off, running, alarm
Generator Alarm:
Aggregate alarm consisting of: low oil
pressure, engine over-temp, engine over-
speed, crank limit, over voltage, low fuel,
water intrusion, pad shear, gas hazard,
test fail
Gas Hazard:
OK, Alarm
Water Intrusion:
OK, Alarm
Pad Shear:
OK, Alarm
Enclosure Door:
Open, Alarm
Ignition Battery Voltage:
10.2 to 15.5Vdc, 100mV resolution
Enclosure Temperature:
-40 to 100°C / -40 to 212°F
Low Fuel:
OK, Alarm
Remote Test:
Start and Stop control input