Specifications for Argus’ CXCI Cordex Controller Integrated Model Continued
Argus Technologies Ltd.
707-492-B1 Rev B WC
Printed in Canada. © 2007 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.
Page 2 of 2
Hardware Specifications, CXCI
CPU: Coldfire
RAM: 8MB
Flash: 4MB
standard
Display:
4 digit LCD
Front Panel Controls:
Display pushbutton toggle switch for voltage (V) or current (A)
CXCI reset switch (soft reset button; hold for 3 seconds to reset IP)
LED’s:
System OK (Green)
Power System Minor Alarm (Yellow)
Power System Major Alarm / Controller Fail (Red)
Audio:
Built-in speaker for alarm and popup message tones
Dimensions:
88mm H x 26mm W x 280mm D
(3.5” H x 1” W x 11“ D)
Weight:
0.34 kg (0.75 lb.)
Mounting:
Integrated on Cordex 2RU series 19” and 23” shelves
Relay Outputs:
Four (4) Form C, 60Vdc 1A maximum
Digital Inputs:
Two (2), 0 to 60Vdc
Analog Inputs:
One (1) DC voltage, 0 to 60Vdc
One (1) DC current, ±50mV
Two (2) temperature, 0 to 20Vdc with power source
Communication Ports:
Ethernet RJ-45, Argus Modem DB-9, CAN [see shelf specifications]
Recommended Signal Wire Sizes (as per UL/CSA)
Wire Size Range:
0.14 to 1.50mm
2
(#26 to #16 AWG)
Temperature Range:
0 to 50°C
(32 to 122°F)
CAUTION – TO REDUCE RISK OF FIRE, USE ONLY 0.14mm
2
(#26 AWG) OR LARGER WIRE.
The above information is valid at the time of publication. Consult factory for up-to-date ordering information.
Specifications are subject to change without notice.