Specifications for Argus Technologies’ CXPS 48-1.8-i 48Vdc Power System Continued
Argus Technologies Ltd.
053-990-B1 Rev A WC
Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.
Page 2 of 3
Connections
Load Connections:
AM breakers (1-pole): 1/4” holes on 5/8” centers
AM breakers (multiple pole): 3/8” holes on 1” centers (with adapter)
Battery Terminations:
AM breakers (1-pole): 1/4” holes on 5/8” centers
AM breakers (multiple pole): 3/8” holes on 1” centers (with adapter)
Alarm/Signal Connections:
0.081mm
2
to 0.55mm
2
(#28 to #20 AWG)
AC Input:
Terminal blocks 2.5mm
2
to 6mm
2
(#14 to #10 AWG),
individual feeds for four modules
Cable Access:
Front and top
Environmental
Operating Temperature:
-40 to +65°C, power derated to 75°C (167°F)
(-40 to 149°F)
Storage Temperature:
-40 to +85°C
(-40 to 185°F)
Humidity:
0 to 95% non-condensing
Elevation:
-500m to 2800m; to 4000m with temperature derated to 40°C
(-1640 feet to 9186 feet; to 13124 feet with temperature derated to 104°F)
Miscellaneous
Number of Rectifiers:
Up to four (4) Cordex 48-1.8kW modules;
Argus #010-602-20 (pre-RoHS #010-580-20)
Distribution Capacity:
Load:
14x 1-pole positions, plug-in type (bullet terminals), AM-style, 5 to 250A
Battery:
4x 1-pole positions, plug-in type (bullet terminals), AM-style, 5 to 250A
Dimensions:
438mm W x 222mm H x 310mm D
(17.24” W x 8.75” H x 12.2” D)
[-000 configuration – excludes mounting brackets, rear cover, and module
handles. For additional options see outline drawings at the rear of this manual.]
MTBF (rectifier module):
>400,000 hours ground benign @ 30°C (86°F)