5.6.2 Distribution
Cabling
Refer to guidelines supplied with the load equipment. Typically distribution cables are sized to provide a 0.5V loop
drop at full load as well as meeting ampacity requirements of the protection fuse or circuit breaker.
Distribution cabling must be terminated with 1/4”–5/8”C lugs for connecting to DCP03.
5.6.3
Breaker Output (Hot) Connections
Connect breaker (hot) output connections before connecting the breaker returns. Secure two hole lugs to the 1/4”
studs (on 5/8” centers) using the supplied hardware with the DCP03. Cables should run directly out the rear of the
distribution center. Refer to Figure 11.
5.6.4
Breaker Return (Ground) Connections
Connect breaker (ground) output connections to the DCP03 ground bar. Secure two hole lugs to the 1/4” holes
(on 5/8” centers) using the supplied hardware with the DCP03. Cables should run directly out the rear of the
distribution center above the breaker (hot) output cables. Refer to Figure 11.
5.6.5
Battery Breaker Connections
Connect battery breaker (hot) connections first using the same guidelines as the load cable installation. Connect
battery ground connections using the same guidelines as load returns. Cables should run directly out the rear of
the distribution center above the breaker (hot) output cables. Refer to Figure 11.
Figure 11–Battery, load, and return connection locations
Battery (hot) connection
Load breaker (hot) connection
System return (ground) bar