Connections, Environmental, Miscellaneous – Alpha Technologies CXPS 48-1T 48V Pos Gnd User Manual
Page 6
Specifications for Argus Technologies’ CXPS 48-1T 48Vdc Power System Continued
Argus Technologies Ltd.
053-392-B1 Rev A WC
Printed in Canada. © 2007 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.
Page 2 of 3
Connections
Load Connections:
AM breakers (1-pole): 1/4” holes on 5/8” centers
AM breakers (multiple pole): 3/8” holes on 1” centers
GMT fuses: screw terminals 0.25mm
2
to 2.5mm
2
(#24 to #14 AWG)
Battery Terminations:
3/8” holes on 1” centers, 4 sets per polarity
Rectifier Terminations:
3/8” holes on 1” centers
Alarm Connections:
0.081mm
2
to 0.55mm
2
(#28 to #20 AWG)
Cable Access:
Top and/or bottom
Environmental
Operating Temperature:
-40 to +75°C, power derated above 65°C (149°F)
(-40 to 167°F)
Storage Temperature:
-40 to +85°C
(-40 to 185°F)
Humidity:
0 to 95% non-condensing
Elevation:
-500m to 2800m; to 4000m with temperature derated to 40°C
(-1640 feet to 9186 feet; to 13124 feet with temperature derated to 104°F)
Miscellaneous
Maximum Number of Rectifiers: Up to five (5) Cordex 48-3.6kW modules
#010-600-20 (pre-RoHS #010-567-20);
NOTES: One rectifier space is occupied by the CXCM4
#018-586-20 (pre-RoHS #018-574-20)
Distribution Capacity:
Tier 1: Up to eighteen (18) 48V, AM plug-in style breakers, 600A maximum
NOTE: Tier may be factory or field configured for eight (8) 48V breaker positions
and ten (10) 24V breaker positions for an optional 48V-24V DC-DC converter
installation
Up to ten (10) 48V, GMT fuse positions
NOTE: Maximum 30A per GMT fuse assembly
Dimensions:
584mm W x 488mm H x 477mm D
(23” W x 19.2” H x 18.8” D)
[for additional options see outline drawings at the rear of this manual]
MTBF (rectifier module):