Output voltage modes, Output current/power modes, Factory ranges and defaults – Alpha Technologies CXPS 48-1T 48V Pos Gnd User Manual
Page 38: 3 factory ranges and defaults
Argus Technologies Ltd.
053-392-C0 Rev A WC
Printed in Canada. © 2007 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.
Page 28 of 31
7.2.1
Output Voltage Modes
Voltage modes can be thought of as modes that, under software control, can directly adjust the output voltage.
The qualification of ‘under software control’ is made because there are processes that occur in the rectifier that
can change the output voltage that do not adjust the output voltage directly (such as the rectifier being in current
limit).
The following table lists four Output Voltage Modes and a description of when they are active:
Output Voltage Modes
Active when…
Float
Output voltage is set to the float voltage setting.
Equalize
Output voltage is set to the equalize voltage setting.
Battery Test
Output voltage is set to the battery test voltage setting.
Safe
Output voltage is set to the safe mode voltage setting.
Table D–Output voltage modes
7.2.2
Output Current/Power Modes
These modes directly affect the output current and power.
The following table lists the four Output Current/Power Modes and a description of when they are active:
Output Current/Power Mode
Active when…
Temperature foldback mode
Output current and power limit have been reduced due to high temperature of the
heatsink or internal ambient temperature sensor.
AC foldback mode
Output current and power limit have been reduced due to low AC input voltage. Note:
this will reduce the risk of tripping an AC breaker due to increased AC current draw as
the AC voltage decreases.
Short circuit foldback mode
Output current limit has been reduced due to a short circuit at the output.
Internal fault foldback mode
Output current limit has been reduced due to an internal fault.
Table E–Output current/power modes
7.3
Factory Ranges and Defaults
The following table lists the rectifier settings/ranges/defaults; changes are made via the CXC:
Setting
Range (minimum to maximum)
Default
Float (FL) Voltage
47.5 – 58.2V
54V
Equalize (EQ) Voltage
49.8 – 60.2V
55V
Battery Test (BT) Voltage
44 – 52V
46V
OVP
See note below – 63V
57V
Current Limit (CL)
23 – 100%
100%
Power Limit (PL)
0 – 100%
100%
Module Start Delay
0 – 250s
1s
System Start Delay
0 – 600s
0s
Low Voltage Alarm (LVA)
42 – 52V
44V
High Voltage Alarm (HVA)
52 – 63V
55.5V
EQ Timeout
1 – 2399h
30h
BT Timeout
1 – 250h
8h
Softstart Ramp-rate
Normal/Fast Normal
CL/PL Alarm
Enable/Disable
Enable
Remote Shutdown
Enable/Disable
Enable
Ramp Test
Enable/Disable
Enable
Table F–Cordex 48-3.6kW factory ranges and defaults
NOTE: OVP cannot be set below the present system/FL/EQ/BT voltage setting or the safe mode voltage of 51.4V.