Converter Output Cabling (+24V HOT Connection)
Terminate the #2 AWG cable with pre-terminated 1/4”-5/8”C lug (With wire marker #16) to the
+24V (hot) output terminal labeled “E3” using hardware supplied with shelf.
Route the un-terminated wire end up in between the system bus bars towards the front of the
distribution center (reference Figure 11 for routing location).
Fish the wire through the existing hole in the glastic insulator of the distribution center
(reference Figure 12 for routing location).
Cut wire to size, strip cable sheath, and crimp supplied 3/8”-1”C lug. Note: This lug must be
crimped after it has been routed through the distribution center.
Attach lug to input bar using the hardware originally used for attaching copper jumper bar.
Converter output (+24V)
wire routing location
Converter output (-GND)
wire connection location