background image

Specifications for Argus’ Cordex Controller Panel/Rack Mount 125/220Vdc

Argus Technologies Ltd.

018-570-B1 Rev B WC

Printed in Canada. © 2005 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 1 of 3

Basic Unit

Input Voltage:

90 to 300Vdc within rated limits


MTBF:

472,000 @ 25°C (77°F)

EMC:

The unit meets requirements of:
ICES-003 Class A
EN 55022 Class A (CISPR 22)
EN 61000-4-2 ESD
EN 61000-4-3 Radiated Immunity
EN 61000-4-4 EFT /Burst
EN 61000-4-6 Conducted Immunity
FCC Part 15 Class A, FCC Part 68


Ground Fault Detection:

0 – 10mA



In accordance with FCC requirements, we provide the following statement as specified in the FCC guidelines for
conformance to Part 15, Class A:

NOTE: This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own
expense.


Any changes or modifications to this equipment not expressly described in this manual could void the FCC
compliance.

Environmental

Operating Temperature:

0 to 65°C standard @ 3000m derate to 55°C @ 4000m
(32 to 149°F derate to 131°F @ 13124ft)
[Optional -40°C]


Storage Temperature:

-20 to 70°C standard
(-4 to 158°F)

-40 to 80°C optional
(-40 to 176°F)


Humidity:

0 to 95% non-condensing


Elevation:

-500 to +4000m
(-1640 to 13124 ft)