Hardware Specifications
CPU: Coldfire
RAM: 8MB
Flash:
4MB standard, 4MB optional
Display:
160 x 160 pixel grayscale LCD
Front Panel Controls:
Reset button and touch panel (display and input device)
LED’s:
System OK (Green)
Power System Minor Alarm (Yellow)
Power System Major Alarm / Controller Fail (Red)
Internal Battery:
3V Lithium CR1616 [Argus part number #185-005-10]
Audio:
Built-in speaker for alarm and popup message tones
Mounting:
Integrated with power system/distribution panel [List 80]
19" and 23" flush rack mounting, 3RU [Default List 81]
Rack Mount Dimensions:
131mm H x 425mm W x 100mm D
(5.1” x H x 16.7” W x 3.9” D)
Weight:
6.2 kg typical [Default List 81]
(13.8 lb.)
Analog Inputs:
1 DC voltage, 1 DC current, 2 temperature, 4 bi-voltage
[sample configuration – other options available]
Ground Fault Detect Alarms:
1
Digital Inputs:
4
Relay Outputs:
8 Form C, 220VDC 0.4A maximum;
8 optional Form C, 60VDC 1A maximum
Communication Ports:
Ethernet Port, 2 x CAN (bus), RS-485, 2 x RS-232,
TNV-1 Telephone Port (with communication expansion board)
Recommended Connection Wire Sizes (as per UL/CSA)
Minimum Wire Size:
0.823 to 0.0507mm
2
(#18 to #30 AWG)
Temperature Range:
0 to 50°C
(32 to 122°F)
CAUTION – TO REDUCE RISK OF FIRE, USE ONLY 0.129mm
2
(#26 AWG) OR LARGER WIRE.