Ac loadcenter power distribution wiring – Alpha Technologies Te41, 48V User Manual
Page 39

1
1
2
2
3
3
4
4
5
5
6
6
D
D
C
C
B
B
A
A
1
J.K
J.K
11
SCHEMATIC, 48V ENCLOSURE W/
747-654-05
P/A
2009/07/08
12:28:06 PM
74765405PA_SHEET1.SCHDOC
Title
SIZE
DWG NO.
Date:
File:
Rev
Sheet
of
Time:
B
DESIGN
DRAWN
CHECKED
APPROVED
22kAIC AC PANEL, FAN DOOR,
V3 DUAL COMPARTMENT
THESE DESIGNS AND SPECIFICATIONS ARE THE PROPERTY OF
ARGUS TECHNOLOGIES AND SHALL NOT BE COPIED OR USED
FOR MANUFACTURING WITHOUT ITS WRITTEN CONSENT.
MATERIAL
TYPE
FINISH
TOLERANCES
SCALE
ISSUE
DATE
09/07
09/07
REVISION
LTR
DESCRIPTION
DATE
APPD
S5
CB3
CB4
CB5
CB6
CB7
CB8
CB9
CB10
CB1
CB2
LINE 2
LINE 1
TO POWER RECTIFIER MODULE #1
LINE 1
LINE 2
NEU
NEUTRAL BUS BAR
EQUIPMENT GROUND BUS BAR
GND
UTILITY POWER
GENERATOR POWER
LINE
BLK - #3/0 AWG (TYP.)
BLK - #3/0 AWG (TYP.)
AC POWER TRANSFER LOADCENTER, 120/240V, 200A, 42 POS, ATS, ICL
TO AIR CONDITIONER UTILITY BOX
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
WHT - #14 AWG
BLK - #14 AWG
BLK -
BLK - #10 AWG
(P/N 020-442-10)
AC LOADCENTER POWER DISTRIBUTION WIRING:
NEUTRAL BUS BAR
BREAKER
BREAKER
NEU
GND
BLK - #3/0 AWG (TYP.)
PANLOC GENERATOR CONNECTOR PANEL
120/240V, 200 AMP, 1 PHASE, 60Hz
AC INPUT POWER CONNECTION
120/240V, 200 AMP, 1 PHASE, 60Hz
3 WIRE + GND
(CUSTOMER CONNECTION)
3 WIRE + GND
15A
200A
200A
NOT USED
GND
60
TO ENCLOSURE MASTER GROUND BAR
(REFER TO SHEET 8)
CABLE ASSEMBLY P/N 875-XXX-36
#2 AWG COPPER (TYP.)
WHERE ELECTRICAL INSPECTION AUTHORITY REQUIRES THE NEUTRAL ASSEMBLY
TO BE CONNECTED TO THE ENCLOSURE, A MAIN BONDING JUMPER MUST BE INSTALLED.
BLK - #3/0 AWG
RED - #3/0 AWG
WHT - #3/0 AWG
GRN - #4 AWG
(CUSTOMER CONNECTION)
GRN - #6 AWG
LINE 2
LINE 1
(REFER TO SHEET 4)
LINE 2
LINE 1
LINE 2
LINE 1
LINE 2
LINE 1
LINE 2
LINE 1
LINE 2
LINE 1
BLK - #10 AWG
BLK - #10 AWG
BLK - #10 AWG
BLK - #10 AWG
BLK - #10 AWG
BLK - #10 AWG
BLK - #10 AWG
BLK - #10 AWG
BLK - #10 AWG
BLK - #10 AWG
BLK - #10 AWG
TO POWER RECTIFIER MODULE #2
(REFER TO SHEET 4)
TO POWER RECTIFIER MODULE #3
(REFER TO SHEET 4)
TO POWER RECTIFIER MODULE #4
(REFER TO SHEET 4)
TO POWER RECTIFIER MODULE #5
(REFER TO SHEET 4)
TO POWER RECTIFIER MODULE #6
(REFER TO SHEET 4)
LINE 2
LINE 1
TO POWER RECTIFIER MODULE #7
(REFER TO SHEET 4)
30A
30A
30A
30A
30A
30A
30A
BLK - #10 AWG
BLK - #10 AWG
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
ATS
CONTROLLER
ATS CONTROL
KEYPAD
TVSS
STRIKESORB
ATS
84
85
86
87
89
90
91
92
93
94
96
97
98
99
60
84
85
86
87
96
97
98
99
15A/125V
J7
J6
HOT
'WHT'
GND
TELCO BOX GFCI AC CONVENIENCE
TEST
RESET
LOAD
NEU
TERMINALS
RECEPTACLE
OUTLET RATING
LINE
TERMINALS
#14 AWG
BLK - #14 AWG
GRN - #14 AWG
(REFER TO SHEET 2)
GRN - #4 AWG
#2 AWG COPPER (TYP.)
GND
TO CORDEX 48-3.6kW RECTIFIER SHELF
88
(REFER TO SHEET 4)
GND
95
GND
102
TO CORDEX 48-3.6kW RECTIFIER SHELF
(REFER TO SHEET 4)
TO CORDEX 48-3.6kW RECTIFIER SHELF
(REFER TO SHEET 4)
GRN/YEL - #10 AWG
GRN/YEL - #10 AWG
GRN/YEL - #10 AWG
GND
109
TO CORDEX 48-3.6kW RECTIFIER SHELF
(REFER TO SHEET 4)
GRN/YEL - #10 AWG
88
95 102 109
89
90
91
92
93
94
CB11
31
32
NOT USED
CB12
33
34
NOT USED
35
36
NOT USED
37
38
NOT USED
39
40
NOT USED
41
42
NOT USED
NEU
GND
LINE
NEU
GND
WHT - #14 AWG
GRN - #14 AWG
44
WHT - #14 AWG
GRN - #14 AWG
14/3 SJ FLEXIBLE CORD
TO GFCI OUTLET
(REFER TO SHEET 2)
NOT USED
NOT USED
NOT USED
15A
15A
43
44
43
45
47
44
46
48
45
46
47
48
BLK - #14 AWG
NOT
USED