Ac loadcenter power distribution wiring – Alpha Technologies Te41, 48V User Manual

Page 39

background image

1

1

2

2

3

3

4

4

5

5

6

6

D

D

C

C

B

B

A

A

1

J.K

J.K

11

SCHEMATIC, 48V ENCLOSURE W/

747-654-05

P/A

2009/07/08

12:28:06 PM

74765405PA_SHEET1.SCHDOC

Title

SIZE

DWG NO.

Date:
File:

Rev

Sheet

of

Time:

B

DESIGN
DRAWN

CHECKED

APPROVED

22kAIC AC PANEL, FAN DOOR,
V3 DUAL COMPARTMENT

THESE DESIGNS AND SPECIFICATIONS ARE THE PROPERTY OF

ARGUS TECHNOLOGIES AND SHALL NOT BE COPIED OR USED
FOR MANUFACTURING WITHOUT ITS WRITTEN CONSENT.

MATERIAL

TYPE

FINISH

TOLERANCES

SCALE

ISSUE
DATE

09/07
09/07

REVISION

LTR

DESCRIPTION

DATE

APPD

S5

CB3

CB4

CB5

CB6

CB7

CB8

CB9

CB10

CB1

CB2

LINE 2

LINE 1

TO POWER RECTIFIER MODULE #1

LINE 1

LINE 2

NEU

NEUTRAL BUS BAR

EQUIPMENT GROUND BUS BAR

GND

UTILITY POWER

GENERATOR POWER

LINE

BLK - #3/0 AWG (TYP.)

BLK - #3/0 AWG (TYP.)

AC POWER TRANSFER LOADCENTER, 120/240V, 200A, 42 POS, ATS, ICL

TO AIR CONDITIONER UTILITY BOX

1

3

5

7

9

11

13

15

17

19

21

23

25

27

29

2

4

6

8

10

12

14

16

18

20

22

24

26

28

30

WHT - #14 AWG

BLK - #14 AWG

BLK -

BLK - #10 AWG

(P/N 020-442-10)

AC LOADCENTER POWER DISTRIBUTION WIRING:

NEUTRAL BUS BAR

BREAKER

BREAKER

NEU

GND

BLK - #3/0 AWG (TYP.)

PANLOC GENERATOR CONNECTOR PANEL

120/240V, 200 AMP, 1 PHASE, 60Hz

AC INPUT POWER CONNECTION

120/240V, 200 AMP, 1 PHASE, 60Hz
3 WIRE + GND

(CUSTOMER CONNECTION)

3 WIRE + GND

15A

200A

200A

NOT USED

GND

60

TO ENCLOSURE MASTER GROUND BAR
(REFER TO SHEET 8)

CABLE ASSEMBLY P/N 875-XXX-36

#2 AWG COPPER (TYP.)

WHERE ELECTRICAL INSPECTION AUTHORITY REQUIRES THE NEUTRAL ASSEMBLY

TO BE CONNECTED TO THE ENCLOSURE, A MAIN BONDING JUMPER MUST BE INSTALLED.

BLK - #3/0 AWG

RED - #3/0 AWG

WHT - #3/0 AWG

GRN - #4 AWG

(CUSTOMER CONNECTION)

GRN - #6 AWG

LINE 2

LINE 1

(REFER TO SHEET 4)

LINE 2

LINE 1

LINE 2

LINE 1

LINE 2

LINE 1

LINE 2

LINE 1

LINE 2

LINE 1

BLK - #10 AWG

BLK - #10 AWG

BLK - #10 AWG

BLK - #10 AWG

BLK - #10 AWG

BLK - #10 AWG

BLK - #10 AWG

BLK - #10 AWG

BLK - #10 AWG

BLK - #10 AWG

BLK - #10 AWG

TO POWER RECTIFIER MODULE #2
(REFER TO SHEET 4)

TO POWER RECTIFIER MODULE #3
(REFER TO SHEET 4)

TO POWER RECTIFIER MODULE #4
(REFER TO SHEET 4)

TO POWER RECTIFIER MODULE #5
(REFER TO SHEET 4)

TO POWER RECTIFIER MODULE #6
(REFER TO SHEET 4)

LINE 2

LINE 1

TO POWER RECTIFIER MODULE #7
(REFER TO SHEET 4)

30A

30A

30A

30A

30A

30A

30A

BLK - #10 AWG

BLK - #10 AWG

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

NOT USED

ATS

CONTROLLER

ATS CONTROL

KEYPAD

TVSS

STRIKESORB

ATS

84

85

86

87

89

90

91

92

93

94

96

97

98

99

60

84

85

86

87

96

97

98

99

15A/125V

J7

J6

HOT

'WHT'

GND

TELCO BOX GFCI AC CONVENIENCE

TEST

RESET

LOAD

NEU

TERMINALS

RECEPTACLE

OUTLET RATING

LINE
TERMINALS

#14 AWG

BLK - #14 AWG

GRN - #14 AWG

(REFER TO SHEET 2)

GRN - #4 AWG

#2 AWG COPPER (TYP.)

GND

TO CORDEX 48-3.6kW RECTIFIER SHELF

88

(REFER TO SHEET 4)

GND

95

GND

102

TO CORDEX 48-3.6kW RECTIFIER SHELF
(REFER TO SHEET 4)

TO CORDEX 48-3.6kW RECTIFIER SHELF
(REFER TO SHEET 4)

GRN/YEL - #10 AWG

GRN/YEL - #10 AWG

GRN/YEL - #10 AWG

GND

109

TO CORDEX 48-3.6kW RECTIFIER SHELF
(REFER TO SHEET 4)

GRN/YEL - #10 AWG

88

95 102 109

89

90

91

92

93

94

CB11

31

32

NOT USED

CB12

33

34

NOT USED

35

36

NOT USED

37

38

NOT USED

39

40

NOT USED

41

42

NOT USED

NEU

GND

LINE

NEU

GND

WHT - #14 AWG

GRN - #14 AWG

44

WHT - #14 AWG

GRN - #14 AWG

14/3 SJ FLEXIBLE CORD

TO GFCI OUTLET
(REFER TO SHEET 2)

NOT USED

NOT USED

NOT USED

15A

15A

43

44

43

45

47

44

46

48

45

46

47

48

BLK - #14 AWG

NOT

USED