beautypg.com

11 hvac default settings – Alpha Technologies Te41, 48V User Manual

Page 36

background image

Argus Technologies Ltd.

057-102-C0 Rev B WC

Printed in Canada. © 2009 Argus Technologies Ltd. ARGUS and CORDEX are trademarks of Argus Technologies Ltd. All Rights Reserved.

Page 25 of 26

11

HVAC Default Settings

Refer to the air conditioner manual (supplied with the system) for operation and maintenance details.

11.1 Air Conditioner/Heater Package

Description Setting
Cooling System ON Temperature

80

qF [26.6qC]

Heating System ON Temperature

60

qF [15.5qC]

HVAC Fail Alarm

(e.g. by dirty filter or failed condensor)

300psi, reset at 225psi

11.2 Enclosure

Temperature

Alarms

Battery Compartment Thermostat

Setting

High Temperature Alarm (Blue)

35

qC (95qF)

Low Temperature Alarm (Red)

-15

qC (5qF)

Power Compartment Thermostat

Setting

High Temperature Alarm (Blue)

65

qC (149qF)

Low Temperature Alarm (Red)

-15

qC (5qF)

11.3 Cooling

Fans

Fan speed is controlled electronically. At temperatures below 30

qC (86qF) they will shut off.