Operation, continued 3.2, Audible alarms and visual indicators, 3 battery – Alpha Technologies FlexPoint FPR1207-F - Technical Manual User Manual
Page 14: 2 audible alarms and visual indicators, 0 operation, continued
3.0 Operation,
continued
3.2 Audible Alarms and Visual Indicators
The table below details the audible alarms and visual indicators of the FPR1207-F.
Table 3-1, Audible Alarms and Visual Indicators
3.3 Battery
Battery construction varies significantly between manufacturers. Alpha Technologies
recommends the use of qualified batteries only.
Part
Description
AX-STDBAT-7
Battery 7.2Ah AGM, 1-year Warranty
AX-LONGBAT-7
Battery 7.2Ah AGM, 3-year Warranty
AX-LONGBAT-8
Battery, Longlife, 8Ah, AGM 3-year Warranty
Condition
Status LED
Audible
Alarm
Description
NORMAL
System LED (GREEN)
N/A
Condition normal; AC powers load,
charges battery.
ON BATTERY
Battery LED (GREEN)
flash
(1) 1s beep on loss
of AC
Input fails; battery powers load.
LOW BATTERY
RED LED blinking
When AC is available,
audible alarms are
suppressed. When AC
fails, 1 beep every 15s.
When battery capacity is < 25%,
unit triggers alarm, or when the
“Battery Emergency Use” button
is pressed.
REPLACE BATT
RED LED steady
2 beeps, every 15
minutes
Every 180 days, the unit will
automatically initiate a battery
test. The test lasts approx. 60
min., and LED lights if battery
replacement is needed.
BATT MISSING
RED LED blinking
N/A
Approximately 20s after battery
removal, system initiates battery
detection routine. Battery detection
runs every 30s when float
charging. Upon verification, alarm
tripped.
010-344-B1-001 Rev. A (2/2014)