Specifications, Mechanical, Environmental – Alpha Technologies Te25xh User Manual
Page 5: Regulatory approvals

Specifications for Argus’ Te25xh Outdoor Power Enclosure
Argus Technologies Ltd.
029-006-B1 Rev D WC
Printed in Canada. © 2006 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologies Ltd. All Rights Reserved.
Page 1 of 2
Mechanical
Dimensions (minimum):
914mm H x 544mm W x 518mm D; see outline drawings,
(36" H x 21.4" W x 20.4" D)
[dimensions vary depending on mounting and other options ordered]
Mounting:
Ground/pedestal or pole
Weight (no batteries/rectifiers): 45.6 kg (100.5 lb.), no riser
55.1 kg (121.5 lb.), with riser
52.9 kg (116.6 lb.), pole mount
Cooling: Fan
cooled
Enclosure: Aluminum,
5052-H32
Internal Rack (optional):
19”, 4RU
Environmental
Operating Temperature:
-40 to +46°C
(-40 to 115°F)
Storage Temperature:
-40 to +85°C
(-40 to +185°F)
Humidity:
0 to 95% non-condensing
Elevation: 3600m,
see
Operating Temperature
(12,000 feet)
Weather Tightness:
NEMA Type 3R
NEMA 4 with closed loop cooling (air exchanger or air conditioner option)
Thermal Performance:
14.6°C above ambient of 24°C @400W
[single cooling fan]
(26.3°C above ambient of 75.2°C)
11.6°C above ambient of 24°C @400W [dual cooling fans]
(20.8°C above ambient of 75.2°C)
Regulatory Approvals
Enclosure Ratings:
CSA/UL Type 3R
Product Safety:
CSA/UL 60950
1
Simulated heat load inside enclosure.