Safety - section a – Gorman-Rupp Pumps S3B65-E6 460/3 861279 thru 1217130 User Manual
Page 4
OM−04151
S SERIES PUMPS
PAGE A − 1
SAFETY
SAFETY − SECTION A
This information applies to the S Series
submersible motor driven pumps and
control boxes.
Because pump installations are seldom
identical, this manual cannot possibly
provide detailed instructions and pre-
cautions for each specific application.
Therefore, it is the owner/installer’s re-
sponsibility to ensure that applications
not addressed in this manual are per-
formed only after establishing that nei-
ther operator safety nor pump integrity
are compromised by the installation.
Before attempting to open or service the
pump:
1. Familiarize yourself with this man-
ual.
2. Lock out incoming power to the
control box to ensure that the
pump will remain inoperative.
3. Allow the pump to completely cool
if overheated.
5. Close the discharge valve (if
used).
This pump is not designed to pump vol-
atile, explosive, or flammable materials.
Do not attempt to pump any liquids for
which you pump is not approved, or
which may damage the pump or endan-
ger personnel as a result of pump fail-
ure. Consult the factory for specific ap-
plication data.
Before connecting any cable to the con-
trol box, be sure to ground the control
box. Refer to the Control Box Manual for
the suggested grounding methods.
The pump motor is designed to be oper-
ated through the control box furnished
with the pump. The control box provides
overload protection and power control.
Do not connect the pump motor directly
to the incoming power lines.
The electrical power used to operate
this pump is high enough to cause inju-
ry or death. Obtain the services of a
qualified electrician to make all electri-
cal connections. Make certain that the
pump and enclosure are properly
grounded; never use gas pipe as an
electrical ground. Be sure that the in-
coming power matches the voltage and
phase of the pump and control before
connecting the power source. Do not
run the pump if the voltage is not within
the limits. If the overload unit is tripped
during pump operation, correct the
problem before restarting the pump.
The electrical power used to operate
this pump is high enough to cause inju-
ry or death. Make certain that the control
handle on the control box is in the OFF
- S3B65-E6 575/3 1199517 and up S3C1 230V 3P 861279 thru 1207589 S3C1 460V 3P 861279 thru 1207589 S3C18 230V 3P 861279 thru 1217140 S3C18 460V 3P 861279 thru 1217140 S4C65-E10 460/3 861279 thru 1142084 S4D65-E10 460/3 861279 thru 1141092 S2F1-E1 230/3 997771 thru 1225728 S2F1-E1 460/3 997771 thru 1225728