Wmk 160 • installation guide (continued), Installation, Step 1 – Extron Electronics WMK 160 User Manual
Page 2: Mount the base plate
2
WMK 160 • Installation Guide (Continued)
Figure 3.
Non-masonry wall mounting
Wall Studs
Cutout for
Electrical
Outlet
Level
Marker for
Pilot Hole
Cutout for
Signal Cable
Access
Mounting
Holes
WMK 160
Base Plate
Installation
NOTE: Refer to local building standards and codes to verify that the installation will meet the regulatory requirements.
Observe all local and national building and safety codes, UL requirements, and ADA accessibility guidelines.
Before installation identify the type of wall (masonry or non-masonry) and the location where the WMK 160 will be installed.
This determines the installation approach and type of fasteners needed to secure the plate to the wall.
Step 1.
—
Mount the Base Plate
Follow the steps within
1A or 1B, as applicable.
NOTE:
The base plate can be installed over an existing electrical outlet (see figure 2).
1A. To mount the WMK 160 onto masonry walls:
i.
Hold the base against the wall, level it, and mark the
positions of four slotted mounting holes (indicated by
+ marks in figure 2). Set the plate aside.
ii.
Using a masonry drill bit, drill 1¾ inch (4.4 cm) deep
pilot holes at the marked locations.
iii.
Screw in ¼ x 1¾ inch masonry screws (not supplied)
until a gap of about 3/8 inch (9 mm) remains between
the wall and the screw heads.
iv.
Align the slotted mounting holes of the base plate
over the installed screws, then slide the plate
down so the screws fit into the slots.
v.
Verify level and position and tighten all the screws to secure
the plate flush to the wall.
Proceed to step 2.
1B. To mount the WMK 160 onto a non-masonry wall:
i.
At the desired site, locate and mark the wall studs.
NOTES:
•
For ideal installation secure the base plate to at least
one wall stud (see figure 3). Drywall KapToggles can be
used for holes not aligned with studs.
•
Always use the widest spacing of screws and
KapToggles.
•
The base plate can be installed over an existing
electrical outlet (see figure 2).
ii.
Hold and level the base plate against the wall and mark
the positions of the slotted mounting holes that are on
the stud lines (see figure 3, indicated by + marks). Where
applicable, mark the mounting holes on the wall for
drywall toggles.
iii
. If the cables are to be run behind the wall to the
WMK 160 location, mark the cutout area on the wall for
the signal cable access hole (see figure 3). Remove the base
plate and set the plate aside.
iv.
Drill 1¾ inch (4.4 cm) deep pilot holes at the hole marks.
v.
Cut out the marked area for cable access.
vi.
At the pilot holes, screw in the screws until a gap of about
3/8 inch (9 mm) remains between the wall and the screw heads.
NOTE:
If using toggle assemblies, see figure 4 for method.
Cutout for
Electical
Outlet
Level
Cutout for
Signal Cable
Access
Marker for
Pilot Hole
WMK 160
Base Plate
Mounting
Holes
Figure 2.
Masonry wall mounting