COMMERCIAL GAS E.I. TROUBLESHOOTING SEQUENCE

For Honeywell Valve

NOTE:

Troubleshooting should be done by qualified service personnel familiar with the start-up and checkout procedure.

TURN GAS SUPPLY OFF

SET THERMOSTAT

TO CALL FOR HEAT

VALVE IS POWERED

(24 VAC NOMINAL)

IS FLUE DAMPER POWERED

ACROSS TERMINALS 3 & 7

IGNITES WARMS UP AND

GLOWS RED

PILOT VALVE OPENS

TURN GAS ON,

PILOT BURNER LIGHTS?

MAIN VALVE OPENS?

SYSTEM ON

CHECK
-

LINE VOLTAGE POWER

-

LOW VOLTAGE TRANSFORMER

-

AQUASTAT (E.C.O.)

-

WIRING

CHECK

-

SWITCH CONTACT SS
OR ES NOT MADE

-

DAMPER FUSE

-

BINDING OR DAMAGED
DAMPER

UNPLUG IGNITER

MEASURE VOLTAGE AT VALVE

TERMINALS. (SEE INSET)

REPLACE IGNITER -

FLAMEROD ASSEMBLY

REPLACE VALVE

MEASURE VOLTAGE TO

VALVE, VOLTAGE MUST BE AT

LEAST 19.5 VAC.

REPLACE IGNITER -

FLAMEROD ASSEMBLY

REPLACE IGNITER SENSOR

AND RETAIN.

RESTART

TROUBLESHOOTING SEQUENCE.

DOES MAIN VALVE OPEN?

DISCARD OLD IGNITER

SENSOR

ELECTRONIC
IGNITION
TERMINALS

REPLACE ENTIRE

DAMPER ASSEMBLY

REPLACE VALVE

CHECK

TRANSFORMER LINE

VOLT SUPPLY

REPLACE VALVE,

SAVE OLD IGNITER

SENSOR FOR

SERVICE

SENSING ROD.
MINIMUM:
.3 MICRO-AMPS

VOLTAGE 24

INSET

NOTE: DO NOT ATTEMPT TO REPAIR THE FLUE DAMPER DRIVE / DEVICE OR MECHANISM.

IF THE UNIT IS DEFECTIVE REPLACE ENTIRE ASSEMBLY.