Figure 8. Vertical Vent Installation

A

B

25mm

(1 in.)

EXHAUST

VENT

TERMINAL

INTAKE

VENT

TERMINAL

203mm (8 in.)

MIN.,610mm

(24 in.) MAX.

25mm

(1 in.)

“A” & “B”: ABOVE SNOW
ACCUMULATION LEVEL
OR 457mm (18 IN.) MIN.
ABOVE ROOF.

Concentric Vent Termination Kit Installation

A concentric Vent termination kit (see Table 2) may be used
for side wall termination installations.

VENT DIA.

KIT

P/N

50mm (2 in.)

KGAVT0701 ULC

6911088

76mm (3 in.)

KGAVT0801 ULC

6911089

Table 2. Concentric Vent Kits

Figure 9 illustrates the Concentric Vent termination kit for
side wall installation. To prevent rain water from entering
the exhaust outlet, slope the vent kit at a downward pitch
of 6.5mm per 1.5m (1/4 in. per 5 ft.) away from the inside
wall. Ensure the combustion air intake location is above the
anticipated snow level.

COMBUSTION AIR

COMBUSTION

AIR

ORIENTATION OF EXHAUST PIPING AND COMBUSTION AIR PIPING RELATIVE
TO EACH OTHER MAY BE VERTICAL (AS SHOWN) OR AT ANY OTHER ANGLE
TO SUIT THE INSTALLATION.

ELBOW (FIELD
SUPPLIED)

SLOPE 6.5mm OVER
1.5m (1/4 in. OVER 5 ft.)

SCREEN INSIDE

STRAP (FIELD
SUPPLIED)

EXHAUST

25mm (1 in.) MAXIMUM

WALL

Figure 9. Concentric Vent Termination (Side Wall Installation)

90° ELBOW
(OPTIONAL)

PIPE NIPPLE
(OPTIONAL)

50mm (2 in.) MAX OR

915mm (36 in.) MIN

242mm (9.5 in.) MAX OR

1.105m (43.5 in.) MIN REF.

Figure 10. Dual Concentric Vent Terminations

Multiple Concentric Vent Installations

When two concentric vent kits are being installed, the vent
hood edges shall be either less than 50mm (2 in.) apart or
more than 915mm (36 in.) apart. Spacings between 50mm
(2 in.) and 915mm (36 in.) are not allowed due to the pos-
sibility of exhaust cross circulation (see Figure 10).

When more than 2 kits are installed only 2 of them shall be
less than 50mm (2 in.) apart. Never install 3 termination kits
together less than 50mm (2 in) apart (see Figure 11).

50mm

(2 in.) MAX

1.105m
(43.5 in.) REF.

915mm
(36 in.) MIN

242mm

(9.5 in.) REF.

Figure 11. Multiple Concentric Vent Terminations