beautypg.com

John Wood Envirosense Power Vent User Manual

Page 11

background image

11

one square inch per 1000 Btu/hr (22 cm

2

/kW) of the total input

of all appliances in the enclosure, but not less than 100 square

inches (645 cm

2

).

If the confined space is within a building of tight construction, air for

combustion and ventilation must be obtained from outdoors. When

directly communicating with the outdoors or communicating through

vertical ducts, two permanent openings, located in the above manner,

should be provided. Each opening should have a free area of not less

than one square inch per 4000 Btu/hr (5.5 cm

2

/kW) of total input of all

appliances in the enclosure. If horizontal ducts are used, each opening

should have a free area of not less than one square inch per 2000 Btu/

hr (11cm

2

/kW) of the total input of all appliances in the enclosure.

a. all aIr froM InsIde BuIldInGs: (See Figure 5 and 6)
The confined space should be provided with two permanent

openings communicating directly with an additional room(s) of

sufficient volume so that the combined volume of all spaces meets

the criteria for an unconfined space. The total input of all gas

utilization equipment installed in the combined space should be

considered in making this determination. Each opening should

have a minimum free area of one square inch per 1,000 Btu per

hour (22 cm

2

/kW) of the total input rating of all gas utilization

equipment in the confined space, but not less than 100 square

inches (645 cm

2

). One opening should commence within 12 inches

(30 cm) of the top and one commencing within 12 inches (30 cm)

of the bottom of the enclosures.

fIGure 6.

B. all aIr froM outdoors: (See Figures 7, 8 and 9)
The confined space should be provided with two permanent

openings, one commencing within 12 inches (30 cm) of the top and

one commencing within 12 inches (30 cm) from the bottom of the

enclosure. The openings should communicate directly, or by ducts,

with the outdoors or spaces (crawl or attic) that freely communicate

with the outdoors.

1. When directly communicating with the outdoors, each opening should

have a minimum free area of 1 square inch per 4,000 Btu per hour

(5.5 cm

2

/kW) of total input rating of all equipment in the enclosure,

see Figure 7.

fIGure 7.

2. When communicating with the outdoors through vertical ducts,

each opening should have a minimum free area of 1 square inch

per 4,000 Btu per hour (5.5 cm

2

/kW) of total input rating of all

equipment in the enclosure, see Figure 8.

3. When communicating with the outdoors through horizontal ducts,

each opening should have a minimum free area of 1 square inch

per 2,000 Btu per hour (11 cm

2

/kW)) of total input rating of all

equipment in the enclosure, see Figure 9.

fIGure 8.

4. When ducts are used, they should be of the same cross-sectional

area as the free area of the openings to which they connect. The

minimum short side dimension of rectangular air ducts should not

be less than 3 inches (7.6 cm), see Figure 9.

fIGure 9.

5. Alternatively a single permanent opening may be used when

communicating directly with the outdoors, or with spaces that

freely communicate with the outdoors. The opening should have

a minimum free area of 1 square inch per 3,000 BTU per hour

(8.3 cm

2

/kW) of total input rating of all equipment in enclosure.

See Figure 9A.

fIGure 9a.

6. Louvers and Grilles: In calculating free area, consideration should

be given to the blocking effect of louvers, grilles or screens

protecting openings. Screens used should not be smaller than 1/4

inch (6.4 mm) mesh. If the free area through a design of louver or

grille is known, it should be used in calculating the size opening

required to provide the free area specified. If the design and free

area is not known, it may be assumed that wood louvers will be

20-25 percent free area and metal louvers and grilles will have

60-75 percent free area. Louvers and grilles should be fixed in

the open position or interlocked with the equipment so that they

are opened automatically during equipment operation.

7. Special Conditions Created by Mechanical Exhausting or

Fireplaces: operation of exhaust fans, ventilation systems,

clothes dryers or fireplaces may create conditions requiring

special attention to avoid unsatisfactory operation of installed

gas utilization equipment.