EN 6.81 Modbus Communication Module 205546 Manual 1212

2.1.4 Configuration Remarks

• The connected units on the Modbus have unique assigned IDs built as

follows:
SRO modbus ID = Instrument modbus ID + modbus ID offset

• ID 0 (broadcast) cannot be used (a broadcast is used for synchronous

transmission of messages to all connected units).

• Available registers are limited to the measured value registers of the indi-

vidual units. Configuration settings cannot be accessed.

• The PLC time-out on the Modbus must be set to 5 seconds from the

SCADA system or the master PLC unit.

• COM module configuration/setup is executed from the “Display Setup/

Communication” menu (see below).

• The “Communication” option in the display menu automatically appears,

when a communication module is connected to the display.

Display Setup

Language

Set Clock

Modbus

Factory settings

Display SW version

Communication

Back

Select

OK

Communication

Baud rate

Parity

Stop bits

Modbus ID offset

Back

Select

OK

Baud rate

300

1200

4800

9600

19200

38400

57600

115200

Back

Select

OK

Parity

Even

Odd

None

Back

Select

OK

Stop bits

1

2

Back

Select

OK

Modbus ID offset

000

Back

Select

>

7 - Display Modbus_RS485 Com Module menu

1/1

8. februar 2010

Default:

9600

Even

1

000

Figure 2. COM Module Configuration

Modbus Communication Modules