A-100nv, 3 external input signal connections, Signal input/output wire color codes – Xylem A-100NV DIGITAL PERISTALTIC PUMPS User Manual
Page 6: Paddlewheel sensor signal input wiring, Page 6
Page 6
5.3 External Input Signal Connections
The A-100NV will accept any one of three different types of external input
signals; 4-20 mA , 0-10 VDC, or frequency. The 4-20mA and 0-10 VDC
loops must be powered. Two types of frequency inputs, AC sine waves
(magnetic coils type outputs) and Digital Square waves (Hall Effect signals,
contact closures), are acceptable. A jumper plug located on the circuit board
is factory pre-set for AC sine wave signals, the jumper must be re-
positioned when digital square wave signals are being used. See page 7,
“Hz input jumper settings”
All wiring connections are to be made inside of the junction box located on
the side of the A-100NV. A liquid-tite connector is supplied and should be
used for the external signal cable. The signal input wires are color coded to
the type of signal being used.
SIGNAL INPUT/OUTPUT WIRE COLOR CODES
WIRE COLOR CODE
INPUT TYPE
MOTOR ON SIGNAL
5-20V DC open collector output
closed while motor is energized
FLOW VERIFICATION SENSOR
4-20 mA
0-10 VDC
ALARM RELAY
connect 2-conductor plug to either
normally open (NO) (factory default)
or normally closed (NC) side of receptacle.
1 AMP MAX @ 125VAC (24VDC)
BROWN (+) & BLACK (-)
PURPLE & PURPLE
WHITE (+) & BLACK (-)
BLUE (+) (non-powered) & BLACK (-)
AC sine wave, TTL, CMOS
ORANGE (+) (non-powered) & BLACK (-)
RED/WHITE (+ 20VDC)
BLACK (-)
YELLOW (signal)
CONTACT (10v @ 2 mA max)
HALL EFFECT, NPN
RED (+) & WHITE (-)
A-100NV
PADDLEWHEEL SENSOR SIGNAL INPUT WIRING
PADDLEWHEEL SENSOR
WIRE COLOR CODE
BLUE-WHITE
PADDLEWHEEL
SENSOR TYPE
MODEL FH
HALL EFFECT SENSOR
BLACK (-)
RED (+)
PUMP INPUT
WIRE COLOR CODE
MODEL FC
AC SINE WAVE SENSOR
BARE (signal)
BLACK (-)
RED (+ 20VDC)
WHITE (signal)
BLACK (-)
RED (+)
BLACK (-)
WHITE (+)