H-3551

Operation 3-3

This setting is the duration of a purge in seconds. The range is 30 to 240 seconds. Allow enough
time for the purge to dissipate and the bubble rate to fall near zero.

Purge Time: [XXX]sec

Pressing on this item will initiate a purge sequence using the current purge settings.

Manual Purge: ENT=Y

This option is used to force a purge every XX days. The limits are 00 to 99 days. If the option is set
to 00 then this option is in affect disabled. A value of 01 will cause a purge every day. The purge
will happen after the first scan past noon.

Timed Prg: [XX] days

This value is the current pressure of the H-3551's internal air tank in psi. This value is informative
only and cannot be edited. The tank pressure should be approximately 3-5 PSI greater than the
orifice pressure.

Tank PSI = XX.X

This value is the difference between the tank pressure and the pressure on the orifice line in psi.
Like tank psi, this value cannot be edited. This value is directly proportional to the bubble rate and
should be approximately 3-5 PSI.

Diff PSI = XX.XX

This display shows the month, day any hour when the last purge sequence was made.

Last Prg=MM/DD HH:MM