Xylem Aquontroller User Manual
Page 52

en
en
en
en
52
50
t1 PowerSupplied
MMA
MMW
R
1=
1,85h
0
65535
Varie
Displays the total time on supply, expressed in proprietary units.
1 unit = 1.82 hours (400=1 month, 4800=1 year).
51
t0 in Operation
MMA
MMW
R
0.1x
sec
0
65535
Varie
Displays the total operating time, expressed in proprietary units. 1 unit = 0.1 seconds.
After 65535 = 1,82 hours the par 50 is increased by one unit.
52
t1 in Operation
MMA
MMW
R
1=
1,85h
0
65535
Varie
Displays the total operating time, expressed in proprietary units.
1 unit = 1.82 hours (400=1 month, 4800=1 year).
53
Time Delta bar
MMA
RW
sec
0
80
5,0
Delay during which the inverter attempts to stop. Enabled when pressure and
frequency are constant. Connected with parameter 47.
54
Pmax NoWater
MMA
R
Watt
30
5000
599
Maximum power input of pump with no flow. Parameter used to monitor pump
operation, particularly in the dry-running condition.
55
Remote On Enable
MMA
RW
N
0000
0001
0000
If ON, the driver is enabled to operate via a digital external command (contact open =
inverter standby).
58
Time StopPump
MMA
MMW
RW
0.1x
sec
29000=
48min
Set the time, over 24 hours, the pump must be stopped. Default 45 minutes. If this
time is exceeded the display shows "leaks". In the sixth event (fixed number), the drive
stops completely. Must be turned off, check the status of the system by eliminating the
losses, if any. Parameter needed to diagnose problems of the drive to stop.
59
C.Time StopPump
MMA
MMW
R
sec
0
1440
Varie
Within 24 hours, shows the time in which the engine is stopped. Parameter used to
diagnose the presence of leakage.
60
Leakages
MMA
MMW
R
N
0
100
Varie
Counts the number of times the continuous pump operating time exceeds the hold
time t0 Pump Off (par 58). By default, so as not to increase the number of leaks, the
pump must not operate for at least 54 mins within a 24 hour timescale. If the "leaks"
message appears, check whether there are leaks in the system or check times and
settings.
62
I DC-Offset
MMA
MMW
RW
N
0
1023
90
Zero-setting the power reading made by the driver (par 46). Parameter only available in
multiple pump systems.
63
TimePmaxNoWater
MMA
MMW
R
sec
Varie
Displays the time elapsed (timer) in the alarm and no water or insufficient pressure.
In the absence of flow with a frequency greater than 45Hz, the timer is incremented.
MMA Version: power less than the value set in par (54) and higher frequency at 45Hz.
MMW Version: Flow valve closed and a frequency above 45Hz.
64* MinTresholdPar %
MMA
MMW
RW
%
Watt
0
90
50
This parameter must be set to default value “50”
65
Tot. ShortC Done
MMA
MMW
RW
N
0
1000
40
Phase-phase or phase-ground short circuit counter. Default value 40.
66
SerialNumber 1
MMA
MMW
….
Serial number
67
SerialNumber 2
MMA
MMW
…
Not in use
72
Nominal Value
MMA
RW
bar
0.3
MMW07: 7.5
2.5
Set the required system pressure (set point).