MMW
13
Drive ResetAllow
MMA
MMW
RW
N
0
100
5
Number of possible driver restarts following alarms relative to driver. When this value is
reached, the driver stops and displays the fault. When this value is reached, turn the
driver off and back on again. In the event of a short circuit, reset the relative short
circuit number
14
Drive ResetDone
MMA
MMW
R
N
0
100
0
Counts the number of restarts performed by the driver following alarms. To reset this
value, turn the driver off and back on again.
15
Kp (PID)
MMA
MMW
RW
N
0
500
8
Proportional coefficient of PID regulator
16
Hydr ResetTime
MMA
MMW
RW
sec
1
1000
10
Delay between motor starts following hydraulic alarms, such as: no water, insufficient
pressure.
17
Hydr ResetAllow
MMA
MMW
RW
N
0
100
5
Number of possible driver restarts following hydraulic alarms.
18
Hydr ResetDone
MMA
MMW
R
N
0
100
Varie
Counts the number of motor restarts following hydraulic alarms, such as: insufficient
pressure, no water.
19
I DC-Bus....
MMA
MMW
R
A
Varie
Average direct current measured on the DC Bus circuit powering the unit.
20
Water Hammer
MMA
MMW
R
N
0
0
Varie
Counts the number of times the measured pressure exceeds twice the set point.
21
fmin start (Hz)
MMA
MMW
RW
Hz
2.99
45.03
10
Minimum motor start and stop frequency. Frequency at which the driver starts
operating (both when starting and stopping) without using ramps.
22
MinimThreshold
MMA
MMW
RW
bar
0
3
0.8
System pressure value below which “minimum threshold”,
The intervention is delayed by the time set in par. (40).
MMW Version:
Minimum threshold with this flow and the non-return valve, integrated, is open. In this
condition the engine is running at 50Hz and is in working condition outside curve.
MMA Version:
Minimum threshold: the alarm occurs when the system pressure does not exceed the
minimum threshold set Par (22).
In the presence of alarm threshold the pump is stopped and the number of attempts
depends on the par. (17).
23
CurrentValu(bar)
MMA
MMW
R
bar
0.3
MMW07: 7.5
MMA07: 10
MMW12: 7.5
MMA12: 10
Varie
Displays the pressure reference PID. This parameter may vary in certain operating
conditions of drive (acceleration, deceleration,stop procedure).., value can be different
from the nominal value/setpoit par(34).
24
SlowRestartNumb.
MMA
MMW
RW
N
0
100
24
Number of pump start attempts following no water alarm. By default, one start attempt
is performed every 50 mins.
25
NoFluxTime
MMA
R
0.1x
Varie
Counts the number of times the no flow condition is present.