En en en en – Xylem Aquontroller User Manual
Page 51

en
en
en
en
51
38
Measured Flux
MMW R
N
0
1023
Varie
Number, coded, used to measure the flow. 
For example: 
0-250 = integrated check valve (MMW) is closed. 
1023 = integrated check valve (MMW) fully open. 
 
39
Treshold Flux
MMW RW
N
0
1023
appr. 1023
This parameter is required in order to perform the correct procedure for switching off 
the pump when the pressure reaches the nominal value required par. (72). 
E.g.: The driver turns off when the measured flow (par 38) is lower than the set 
threshold (par 39). If 1023 is also set, the driver stop procedure does not consider the 
flow. In this case the AQUONTROLLER version MMA procedure is used. 
Note: if set 1023, MMW transforms to MMA 
40
TimeMinThreshold
MMA 
MMW 
RW
sec
1
1200
20
Delay time to enter the condition of "minimum threshold" (par.22), end of curve pump 
operation. The pump remains stationary for the time set in par. (16) and attempts are 
made to restart at the value set in par. (17). 
41
C.Time NoWater
MMA 
MMW 
R
sec
0
Varie
In the presence of a fault, it displays the delay prior to entering the “No water” (par 
42) alarm condition and increases the number of no-water alarms counter, par(24). 
Non-return valve closed 
42
LackOfWaterTime
MMW RW
sec
1
1200
25
Delay before entering the “No Water" alarm condition with non-return valve closed and 
motor running at 50Hz. 
The alarm trips when the pressure falls below the minimum threshold (par 22) but 
measures zero flow (par 38). 
43
f Output (Hz)
MMA 
MMW 
R
Hz
Varie
Frequency applied to the motor
44
Voltage Motor
MMA 
MMW 
R
N
0
32767
Varie
Voltage applied to the motor (proprietary unit of measurement: Umax=32767)
45
C.TimeMinThresh.
MMA 
MMW 
R
sec
0
Par.(40)
Varie
The delay prior to entering the Minimum threshold alarm condition (par 22) and flow 
present is displayed. Moto runs at50Hz, non return valve open. 
46
Power (Watt)
MMA 
MMW 
R
W
0
2500
Varie
Pump power input (Par 1).
47
Length Perturb.
MMA
RW
sec
0.1
20
1
When the delay elapses, Delta bar (par 53) checks the pressure value for the set time. If 
it remains where it is or increases, the drive stops. 
48
Nom MotorCurrent
MMA 
MMW 
RW
A
0.45
MMW07: 12 
MMA07: 12 
MMW12: 719 
MMA12: 19
4.5
Nominal motor current of the motor (see the motor rating plate). The maximum power 
of the AQUONTROLLER (see plate) must not be exceeded. For longer cable length 
(>50m) the value can be increased for 10%. 
49
t0 PowerSupplied
MMA 
MMW 
R
0.1x 
sec 
0
65535
Varie
Displays the total time on supply, expressed in proprietary units. 1 unit = 0.1 seconds. 
After 65535 = 1,82 hours the par 50 is increased by one unit. 