Appendix b: fuse and wire sizing, Appendix c: weights and dimensions – Xylem IM244R04 SPD Plus Variable Speed Pump Control User Manual
Page 31
31
APPENDIX B: FUSE AND WIRE SIZING
(CONTINUED)
SPD PLUS OUTPUT WIRE SIZING CHARTS
Maximum Allowable Conductor Length (50˚C Ambient, 5% drop)
Controller
Ratings
Conductor Size for 75˚C Rated Wire
(Lengths in Bold Require 90˚C Rated Wire)
Controller
Output
Motor
HP
Motor
FLA
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400 500 600 750 1000
230V
20
54
408
522
667
846
1075
1364
1726
2181
2580
3100
3627
25
68
404
519
662
843
1074
1362
1723
2041
2454
2873
3289
30
82
420
539
689
881
1120
1420
1684
2026
2374
2720
3392
40
96
450
579
743
947
1204
1430
1722
2019
2316
2890 3484
50
116
603
771
984
1172
1413
1659
1906
2382 2871 3610
60
130
679
869
1038
1253
1472
1693
2118 2553 3214
460V
40
53
834
1066 1360
1726
2191
2780
3519
50
70
782 1005 1283
1635
2083
2643
3346
3963
60
80
865 1108 1416
1809
2298
2914
3455
75
96
901 1158 1487
1894
2408
2861
3444
100
127
1087 1393 1783 2128 2568
3018
3469
575V
40
43
802
1315
1671
2124 2689 3407
50
54
1017 1301 1661
2108
2676
3396
60
64
1076 1379 1756 2234
2842
3602
75
76
1146 1466 1871
2388
3032
3842
100
101
1366 1758
2242
2853
3391
APPENDIX C: WEIGHTS AND DIMENSIONS
CONTROLLER DIMENSIONS
NEMA 1 Enclosures
NOTE
Controllers with an N1 suffix have a NEMA 1
enclosure and are rated for indoor use only.
NEMA 1 Enclosure Dimensions
Ref.
R4
R5
R6
mm
in
mm
in
mm
in
W
203
8.0
265
10.4
300
11.8
H
596
23.4
602
23.7
700
27.6
H2
583
23.0
578
22.8
698
27.5
H3
689
27.1
739
29.1
880
34.6
D
262
10.3
286
11.3
400
15.8