APPENDIX B: FUSE AND WIRE SIZING
FUSES
Branch circuit protection must be provided by the end
user and sized per national and local electric codes.
The following tables provide fuse recommendations
for short circuit protection on the drive's input power.
The rated fuse currents given in the tables are the
maximums for the mentioned fuse types. If smaller
fuse ratings are used, check that the fuse Arms current
rating is larger than the input current.
Check that the operating time of the fuse is below
0.5 seconds. The operating time depends on the
fuse type, the supply network impedance as well as
the cross-sectional area, material and length of the
supply cable. In case the 0.5 seconds operating time
is exceeded with the gG or T fuses, ultra rapid (aR)
fuses will in most cases reduce the operating time to
an acceptable level.
Input
Voltage
Model
Number
Input
Current
(Arms)
Mains
Fuse Size
(UL Class T)
230V
SPD20400
114
150
SPD20400F
143
200
SPD20400N1
114
150
SPD20500
143
200
SPD20500F
178
250
SPD20500N1
143
200
SPD20600
178
250
SPD20600F
221
300
SPD20600N1
178
250
460V
SPD40400
59
80
SPD40400F
72
90
SPD40400N1
59
80
SPD40500
72
90
SPD40500F
96
125
SPD40500N1
72
90
SPD40600
96
125
SPD40600F
96
125
SPD40600N1
96
125
SPD40750
124
175
SPD40750F
124
175
SPD40750N1
124
175
SPD41000
157
200
SPD41000F
157
200
SPD41000N1
157
200
575V
SPD50400N1
52
60
SPD50500N1
77
100
SPD50600N1
77
100
SPD50750N1
99
150
SPD51000N1
144
200