Technical table, General description – Powersolve ESB101 Series User Manual
Page 2
Powersolve Electronics Ltd. Unit 8A, Arnhem Road, Newbury. RG14 5RU.
United Kingdom
p.2/4 12.12D
Phone 0044(0)1635 521858 - Fax 0044(0)1635 523771
– www.powersolve.co.uk – [email protected]
(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)
Technical Table
Model
ESB101.16
ESB101.23
ESB101.23S
ESB101.33
ESB101.LED.230Vac
ESB101.LED.115Vac
ESB101.23S.115Vac
Article Number
3041081001 3041081002 3041081003 3041081004
3041081005
3041081006
3041081007
Peak Current
Limiting ±6%
16A
23A
23A
33A
48A
43A
23A
R.M.S Current
Limiting ±6%
11,3A
16,3A
16,3A
23,3A
33,9A
30,4A
16,3A
Allowed Capacitive
Load (max.)
1.500µF
2.000uF
2.000uF
4.000µF
6.000uF
10.000uF
4.000µF
Limiting Time
(T
on
Power On)
300(±50)ms 300(±50)ms 500(±50)ms 300(±50)ms
300(±50)ms
300(±50)ms
500(±60)ms
Release Time
(T
off
Low Voltage)
500(±50)ms 500(±50)ms 800(±80)ms 500(±50)ms
550(±50)ms
550(±50)ms
900(±80)ms
Limiting Interval
[T
interval
for AC
cont.
)
≥ 900ms
≥ 900ms
≥ 1400ms
≥ 900ms
≥ 900ms
≥ 900ms
≥ 1400ms
Smallest advisable
Circuit Breaker
at 30°C
A6A
B4A
Z6A
A10A
B6A
Z10A
A10A
B6A
Z10A
A13A
B8A
Z13A
B13A
A16A
B13A
Z16A
A10A
B6A
Z10A
AC Input Range
184-265Vac
90-130Vac
AC Continous Range
230Vac
115Vac
Line Frequency
16 ⅓ Hz – 440Hz
16 ⅓ Hz – 440Hz
Switch-On Voltage
144Vac
79Vac
AC Lower Margin
52Vac (AC dump / drop)
28Vac (AC dump / drop)
AC Continous Current
16A continous
AC Peak Current
165A for 20ms / 800A for 200us (even while switching internal bypass relay)
Power Supply
item is self-powering
Current Consumption
19mA constant at continous operation
Limiting Cycles
3 cycles/minute
Internal Protection
Thermal fuse protects overload & fire
Cooling
Natural convection
Operation Temp.
Ambient temperature -40°C...+70°C continuous / +75°C short time
Storage Temp.
-40°C...+85°C for 2 years
EMI
EN55022 class B
EMS
EN61000-6-2,3
Safety Norms
IEC/EN60950-1 in accordance with cUL60950
Safety Class II
VDE0805, VDE0100/ÖVE8001
MTBF Calculation
300.000h (IEC/EN61709, Siemens SN29500)
MTTF Calculation
384.000h (+30°C) (IEC/EN61709, Siemens SN29500)
Humidity
95% (+25°C) not condensing
Pollution Degree
2 (IEC/EN50178)
Environmental
thermal environment 3K3, mechanics 3M4 (IEC/EN60721)
Altitude max.
4000m (13123 ft.) above sea level
Dimension (BxHxT)
(2TE)36,5x110x62mm
Hausing Parameters
UL94V-0 ABS IP20 DIN/EN43880 universal housing for DIN/VDE0603 cutout box and for wall mount
DIN-Rail
DIN-Rail TS35mm DIN/EN60715 (TS35/7,5 und TS35/15)
Weight
121g / 0,27 lb
Connections
Spring-type terminal with cable protection 0,5...6mm² 21…10AWG according with IEC/EN60664-1, IEC/EN61984
General Description:
The CAMTEC ESB101-series are the 2nd generation and cost effective inrush current limiters. The limiters are made for
115/230Vac 16A networks. The line frequency range is 16⅓Hz – 440Hz. The ESB101-Limiter shall be located between the
line-switcher/contactor and the load (p.2/Fig.1). The ESB-models are designed for inductive and capacitive loads. In the
moment of switching-on the system the inrush current of the installed load will be limited for the defined time T
on
(p.4/Fig.5). Independent from the previous inrush level; the current limiting is always strict. After T
on
elapses the current
limiting circuit of the ESB101 will be bypassed. Then the load is directly connected to the AC. The electrical network can
be stressed with current loads as normal (e.g. motors, pumps). If an AC dump overshoots the defined time T
off
, it will be
detected by the ESB101 (p.4/Fig.6). As soon as the AC recovers the inrush will be limited, again (p.2/Fig.3 & 4). The
ESB101-models provide an internal temperature control. In case of a failure the device shuts down to safely prevent
from overheating or burning.