5.2.10 S10 Terminal DI6 operation in traveling movement application

Input DI6 is used for external faults as motor thermal protection. The function of the DI6 input can be changed
according to the following table. The NTC thermistor can be used with external thermistor relay.

CAUTION

Wrong parameter setting may accidentally deactivate the DI6 input, possibly
causing hazardous situations.

Switch S10- 1

Terminal DI6 operation

DI6 Function

Description

0

In use

Normally a voltage is present at the input. When the voltage drops:

Starting the motor is not possible

During running the motor current is cut off immediately

External stop fault code is shown with LED.

1

Not in use

When the input is deactivated, it does not have any effect in the operation of the device.