R&M Materials Handling VARIABLE SPEED CONTROLS ControlMaster NXT Service Manual User Manual
Page 32
R&M Materials Handling, Inc.
4501 Gateway Boulevard
Springfield, Ohio 45502
P.: (937) 328-5100
FAX: (937) 325-5319
32/53
R&M Materials Handling, Inc. reserves the right to alter or amend the above information without notice.
5.2.10 S10 Terminal DI6 operation in traveling movement application
Input DI6 is used for external faults as motor thermal protection. The function of the DI6 input can be changed
according to the following table. The NTC thermistor can be used with external thermistor relay.
CAUTION
Wrong parameter setting may accidentally deactivate the DI6 input, possibly
causing hazardous situations.
Switch S10- 1
Terminal DI6 operation
DI6 Function
Description
0
In use
Normally a voltage is present at the input. When the voltage drops:
Starting the motor is not possible
During running the motor current is cut off immediately
External stop fault code is shown with LED.
1
Not in use
When the input is deactivated, it does not have any effect in the operation of the device.