beautypg.com

Warning, Ac b, Ba c – Peerless-AV PP740 - Installation User Manual

Page 6: Installation to solid concrete and cinder block

background image

6 of 46

ISSUED: 01-15-08 SHEET #: 095-9282-6 02-01-12

Installation to Solid Concrete and Cinder Block

Level and use wall plate as template to mark center
of holes.

Drill two 5/16" (8 mm) dia. holes to a

minimum depth of 2.5" (64 mm). Insert anchors (B)
in holes fl ush with wall. Place wall mount (A) over
anchors and secure with wood screws (C). Make
sure wall mount is level, and tighten all fasteners.

A

C

B

WALL PLATE

SOLID CONCRETE

CINDER BLOCK

2

CUT

A

W

A

Y

VIEW

INCORRECT

CORRECT

wall

plate

wall

plate

plaster/
dry wall

plaster/
dry wall

concrete

concrete

1

3

B

Drill holes and insert anchors (

B

).

Place plate (A) over anchors (B) and secure with screws (C).

Tighten all fasteners.

2

B

A

C

concrete
surface

• When installing Peerless wall mounts on cinder block, verify that you have a minimum of 1-3/8" (35 mm) of actual

concrete thickness in the hole to be used for the concrete anchors. Do not drill into mortar joints! Be sure to mount
in a solid part of the block, generally 1" (25 mm) minimum from the side of the block. Cinder block must meet ASTM
C-90 specifi cations. It is suggested that a standard electric drill on slow setting is used to drill the hole instead of a
hammer drill to avoid breaking out the back of the hole when entering a void or cavity.

• Concrete must be 2000 psi density minimum. Lighter density concrete may not hold concrete anchor.

• Make sure that the wall will safely support four times the combined load of the equipment and all attached hardware

and components.

WARNING

• Tighten screws so that wall plate is fi rmly attached,

but do not overtighten. Overtightening can damage
screws, greatly reducing their holding power.

• Never tighten in excess of 80 in. • lb (9 N.M.).

• Always attach concrete expansion anchors directly

to load-bearing concrete.

• Never attach concrete expansion anchors to

concrete covered with plaster, drywall, or other
fi nishing material. If mounting to concrete surfaces
covered with a fi nishing surface is unavoidable (not
evaluated by UL), the fi nishing surface must be
counterbored as shown below. Be sure concrete
anchors do not pull away from concrete when
tightening screws. If plaster/drywall is thicker than
5/8" (16 mm), custom fasteners must be supplied by
installer (not evaluated by UL).

WARNING