7 ac output 3.8 battery and charger – PowerWalker VFI 30000TP 3_3 BE User Manual
Page 15
10
EN
3.7 AC output
3.8 Battery and Charger
Internal battery package Panasonic LC-RW 1245W / CSB HR 1234WF2
Dimensions
94*151*64.5/pc(Panasonic) 94*151*65/pc(CSB)
Strings
2 x 16
Charger Input Protection 8 A fuse
Rated Charge Voltage ±216V Default for Integrated bettery
Initial Charging Current 4.5A
Battery Leakage < 3.5mA
Battery protection
125A Breaker
Stored energy time
up to 860s At Rated liner Load,25℃ up to 540s At Rated liner Load,25℃
Restored energy time <8Hours Up to 90% charge
30A Fuse*3 For PCBA level 30A Fuse*2*3 For PCBA level
Max discharging current 87A Ubat=308VDC,Full RCD load 116A Ubat=308VDC,Full RCD load
Frequency 50/60HZ
Active power 24KW 32KW
Number of phases 3-phases + N
VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI
Overload
capability
(Mains
available)
Voltage (L-N) 220/230/240 VAC
110% 10 minutes minimum, then transfer to bypass and alarm 125% Load>150% 1 minutes minimum, then transfer to bypass and alarm then transfer to bypass and alarm then transfer to bypass and alarm then transfer to bypass and alarm then transfer to bypass and alarm 110% 125% Load>150% Overload VFI 30000TP 3/3 BE/BI VFI 40000TP 3/3 BE/BI
0.5 seconds minimum,
10 minutes minimum,
1 minutes minimum,
0.5 seconds minimum,
capability
(battery
available)