3 maintenance, servicing and faults – PowerWalker VFI 1000T LCD User Manual

Page 6

background image

3

Ensure that no liquid or other foreign objects can enter the UPS.

Do not remove the enclosure. This system is to be serviced by

qualified service personnel only.

Remove the protective panel only after disconnecting the terminal

connections.

Use No. 12AWG (for 3K/KS output terminal), 9

0℃

copper wire

and 12 lb-in Torque force when connecting to terminal block.

Use No. 12 AWG (for 3KS input wire), 90

copper wire and

4.4 lb-in Torque force when connecting to terminal block.

1.3 Maintenance, servicing and faults

The UPS operates with hazardous voltages. Repairs may be

carried out only by qualified maintenance personnel.

Caution - risk of electric shock. Even after the unit is

disconnected from the mains power supply (building wiring

socket), components inside the UPS are still connected to the

battery which are potentially dangerous.

Before carrying out any kind of service and/or maintenance,

disconnect the batteries. Verify that no current is present and no

hazardous voltage exists in the capacitor or BUS capacitor

terminals.

Batteries must be replaced only by qualified personnel.

Caution - risk of electric shock. The battery circuit is not isolated

from the input voltage. Hazardous voltages may occur between

the battery terminals and the ground. Verify that no voltage is

present before servicing!

Batteries have a high short-circuit current and pose a risk of

shock. Take all precautionary measures specified below and

any other measures necessary when working with batteries:

remove all jewellery, wristwatches, rings and other metal

objects