30

of UPS system are
reversed

system.

EPO active

EPO function is
enabled

Turn off the EPO switch.

Bus fault

UPS internal fault

Notify dealer

Inverter fault

UPS internal fault

Notify dealer

Over temperature
fault

Over temperature

Check the ventilation of the
UPS, check the ambient
temperature and ventilation.

Inverter short

Output short circuit

Remove all the loads. Turn
off the UPS. Check whether
the output of UPS and loads
is short circuit. Make sure
the short circuit is removed,
and the UPS has no internal
faults before turning on
again.

Bus short

UPS internal fault

Notify dealer

Please have the following information at hand before calling the

After-Sales Service Department:

1. Model number, serial number

2. Date on which the problem occurred

3. LCD display status, Buzzer alarm status

4. Utility power condition, load type and capacity, environment

temperature, ventilation condition

5. The information (battery capacity, quantity) of external battery pack

if the UPS is “L” model

6. Other information for complete description of the problem